Precautions When Connecting Electrical Wiring - Daikin RXYSQ6T7Y1B9 Installer's Manual

Vrv iv-s system air conditioner
Hide thumbs Also See for RXYSQ6T7Y1B9:
Table of Contents

Advertisement

6 Installation
The transmission wiring outside the unit should be wrapped and
routed together with the field piping.
Branches
Maximum number of branches
for unit-to-unit cabling
Transmission wiring
Maximum wiring length
(= distance between outdoor and
furthest indoor unit)
Total wiring length
(= distance between outdoor and
all indoors)
If the total transmission wiring exceeds these limits, it may
result in communication error.
No branching is allowed after branching.
A
C
B
A
Outdoor unit
B
Indoor unit
C
Central user interface (etc...)
a
Main line
b1, b2, b3
Branch lines
c1, c2
No branch is allowed after branch
6.8.2
Precautions when connecting electrical
wiring
DANGER: RISK OF ELECTROCUTION
WARNING
All field wiring and components must be installed by a
licensed electrician and must comply with the applicable
legislation.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category  III
condition, shall be installed in the fixed wiring.
Installer and user reference guide
24
9
Vinyl cords with 0.75 to 1.25 mm²
sheath or cables (2‑core wires)
300 m
600 m
b1
b2
c1
b3
c2
a
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1 metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Do not operate the unit until the refrigerant piping is
complete. Running the unit before the piping is ready will
break the compressor.
NOTICE
If the power supply has a missing or wrong N-phase,
equipment will break down.
NOTICE
Do NOT install a phase advancing capacitor, because this
unit is equipped with an inverter. A phase advancing
capacitor will reduce performance and may cause
accidents.
NOTICE
Never remove a thermistor, sensor, etc., when connecting
power wiring and transmission wiring. (If operated without
thermistor, sensor, etc., the compressor may break down.)
NOTICE
▪ The reversed phase protection detector of this product
only
functions
when
Consequently
reversed
performed during normal operation of the product.
▪ The reversed phase protection detector is designed to
stop the product in the event of an abnormality when
the product is started up.
▪ Replace two of the three phases (L1, L2, and L3)
during reverse-phase protection abnormality.
the
product
starts
up.
phase
detection
is
not
RXYSQ6T7Y1B9
VRV IV-S system air conditioner
4P404677-1A – 2016.03