Technibel Climatisation CAFM1V Installation Instructions Manual page 54

Multiset system air conditioner
Table of Contents

Advertisement

06-062 Mini ECO-i II for Technibel
b) Lift the indoor unit, and place it on the washers
through the notches, in order to fix it in place.
(Fig. 3-90)
c) Tighten the 2 hexagonal nuts on each suspen-
sion bolt to suspend the indoor unit as shown in
Fig. 3-91.
NOTE
The ceiling surface is not always level. Please confirm
that the indoor unit is evenly suspended. For the
installation to be correct, leave a clearance of about
10 mm between the ceiling panel and the ceiling sur-
face and fill the gap with an appropriate insulation or
filler material.
(8) If the tubing and wiring are to go towards the rear
of the unit, make holes in the wall. (Fig. 3-92)
(9) Measure the thickness of the wall from the inside
to the outside and cut PVC pipe at a slight angle
to fit. Insert the PVC pipe in the wall. (Fig. 3-93)
SPAFM
2/8/06
4:32 PM
Page 54
54
Fig. 3-90
Fig. 3-91
NOTE
The hole should be made at a slight downward slant
to the outside.
Indoor
side
Fig. 3-92
PVC pipe (locally purchased)
INSIDE
Cut at slight angle
Fig. 3-93
Outdoor
side
OUTSIDE
Wall
PVC pipe
Slight
angle