06-062 Mini ECO-i II for Technibel
CAUTION
CAFM1V
G
Do not install an air bleeder as this may cause
water to spray from the drain pipe outlet.
(Fig. 3-12)
G
If it is necessary to increase the height of the
drain pipe, the section directly after the con-
nection port can be raised a maximum of 50
cm. Do not raise it any higher than 50 cm, as
this could result in water leaks. (Fig. 3-13)
G
Do not install the pipe with an upward gradient
from the connection port. This will cause the
drain water to flow backward and leak when the
unit is not operating. (Fig. 3-14)
G
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe
should not be allowed to hang unsupported
from its connection to the unit. Fasten the pipe
to a wall, frame, or other support as close to
the unit as possible. (Fig. 3-15)
G
Provide insulation for any pipes that are run
indoors.
2/8/06
4:32 PM
Page 32
32
Air bleeder
Fig. 3-12
30 cm or less (as short as possible)
50 cm or less
Fig. 3-13
Upward gradient prohibited
Fig. 3-14
Support
pieces
Fig. 3-15