Technibel Climatisation CAFM1V Installation Instructions Manual page 124

Multiset system air conditioner
Table of Contents

Advertisement

06-062 Mini ECO-i II for Technibel
1. Insert a screwdriver or similar tool into the notch at
the bottom to remove the receiver nameplate.
2. Cut a section out of the ceiling along the provided
paper pattern (95 × 51 mm).
CAFM1V
3. Pass the wire through the provided mounting
bracket and insert the bracket into the installation
hole. (Fig. 11-26)
4. Use bracket parts (A) and (B) to securely grip the
ceiling material. (Fig. 11-27)
5. Connect the receiver wire (2-core) to the wire from
the indoor unit.
(Refer to "Wiring the Receiver Unit.")
Check the terminal number on the indoor unit
before wiring the receiver unit and be sure not to
wire incorrectly. (The unit will be damaged if high
voltage, such as 200 VAC, is applied.)
6. Adjust the provided spacers so that they are sev-
eral millimeters larger than the thickness of the
ceiling material. Pass the 2 supplied screws (M4 ×
40) through the spacers and tighten them enough
to hold the receiver unit in place.
7. Return parts (A) and (B) through the gap between
the ceiling and receiver unit so that they are con-
tained in the openings. Then tighten the screws.
Do not tighten the screws excessively. This may
result in damage or deformation of the case. Tight-
en to the point where the receiver unit can be
DSAFM
moved slightly by hand. (Fig. 11-28)
8. Reattach the nameplate.
DSAFMHP
KFM
KFMNC
2/8/06
4:32 PM
Page 124
124
Fig. 11-26
Part (A)
Part (B)
Fig. 11-27
Fig. 11-28