Download Print this page

Battery Connection - Tripp Lite PowerVerter APSX6048VR Owner's Manual

Apsx pure sine wave dc-to-ac inverter/charger
Hide thumbs Also See for PowerVerter APSX6048VR:

Advertisement

Available languages

Available languages

Battery Connection

Connect your Inverter/Charger to your batteries using the following procedures:
• Connect DC Wiring: Though your
Inverter/Charger is a
h i g h - e f f i c i e n c y
converter
of
electricity, its rated
output capacity is
limited by the length
DC Connectors
and gauge of the
cabling running from the battery to the unit.
Use the shortest length and largest diameter
cabling (maximum 9.3 mm diameter (2/0
AWG)) to fit your Inverter/Charger's DC
Input terminals. Shorter and heavier gauge
cabling reduces DC voltage drop and allows
for maximum transfer of current. Your
Inverter/Charger is capable of delivering
peak wattage at up to 200% of its rated
WARNING! • Failure to properly ground your Inverter/Charger to earth ground may result in a lethal
electrical shock hazard.
• Never attempt to operate your Inverter/Charger by connecting it directly to output from an alternator
rather than a battery or battery bank.
• Observe proper polarity with all DC connections.
Series Connection
In a series connection, your Inverter/Charger's Nominal DC Input Voltage must match the number of batteries multiplied by their voltage.
For example, a 48V DC Inverter/Charger requires either four 12V batteries connected in series (48 = 4 × 12) or eight 6V batteries
connected in series (48 = 8 × 6).
Contact Tripp Lite technical support for assistance with additional parallel, series or series/parallel connections.
Figure below illustrates 12V batteries with a 48V Inverter/Charger.
1
12 Volts
Multiple Battery Connection (Series)
1
2
3
Earth Ground
Battery
(2/0 AWG) to Fit Terminals
continuous wattage output for brief periods
of time. Heavier gauge cabling should be
used when continuously operating heavy
draw equipment under these conditions.
Tighten your Inverter/Charger and battery
terminals to approximately 3.5 Newton-
meters
efficient
excessive heating at this connection.
Insufficient tightening of the terminals could
void your warranty. See table below for
recommended cable sizing chart.
• Connect Ground: Using a 3.15 mm
diameter (8 AWG) wire or larger, directly
connect the Main Ground Lug to earth
ground. See the Feature Identification
Maximum Recommended DC Cable Length
V DC
Output Power
24V
3000W
48V
6000W
2
2
2
12 Volts
12 Volts
3
UL-Listed Fuse & Fuse Block (mounted within 450 mm of the battery)
of
torque
to
create
connection
and
to
prevent
Wire Diameter (Gauge)
8.3 mm (0 AWG)
Maximum Distance from Battery to Unit
13 m (42 ft)
Do not use
2
4
12 Volts
9
section to locate the Main Ground Lug on your
specific
Inverter/Charger
installations must comply with national and
local codes and ordinances.
• Connect Fuse: Tripp Lite recommends
that you connect your Inverter/Charger's
an
positive DC Terminal directly to a fuse and
fuse block within 450 mm of the battery.
The fuse's rating must equal or exceed the
Minimum DC Fuse Rating shown on your
Inverter/Charger's nameplate. See diagrams
below for proper fuse placement.
9.3 mm (2/0 AWG)
16 m (52 ft)
32 m (105 ft)
48V Inverter/Charger
4
Large Diameter Cabling, Maximum 9.3 mm diameter
model.
All

Advertisement

loading

This manual is also suitable for:

Powerverter apsx3024sw