Monthly Maintenance; Battery Installation; Battery Connection - Tripp Lite APS1012SW Owner's Manual

Sine wave dc-to-ac inverter/chargers
Table of Contents

Advertisement

Available languages

Available languages

3. Battery

3.2 Monthly Maintenance

• Check the level of the electrolyte of each Wet-Cell battery cell monthly after the batteries have been charged. It should be
about one-half inch above the top of the plates, but not completely full. Note: This is not necessary on maintenance-free
batteries.
• Check the battery connections for tightness and corrosion. If any corrosion is found, disconnect the cables and clean them
with a mild solution of baking soda and water. DO NOT ALLOW THE SOLUTION TO ENTER THE BATTERY. When finished, rinse
the top of the battery with clean water.
• To reduce corrosion on the battery terminals, coat them with a thin layer of petroleum jelly or anti-corrosion grease. Do not
apply any material between the terminal and the cable lugs; the connection should be metal to metal. Apply the protective
material after the bolts have been tightened.

3.3 Battery Installation

Caution! Batteries can produce extremely high currents. Review both the important safety
instructions at the beginning of this manual and the battery supplier's precautions before installing
the inverter and batteries.
3.3.1 Battery Location
Batteries should be installed in an accessible location with good access to the battery caps and terminals. At least two feet
(24 in.) of overhead clearance is recommended. They must be located as close as possible to the inverter. Do not locate the
inverter in the same compartment with non-sealed batteries (sealed batteries are acceptable). The gasses produced by these
batteries during charging are very corrosive and will shorten the life of the inverter.
3.3.2 Battery Enclosure
Batteries should be installed in a ventilated, locked enclosure or room. The enclosure should be well-ventilated to prevent
accumulation of hydrogen gasses that are released in the battery charging process. The enclosure should be made of acid
resistant material or coated with an acid resistant finish to resist corrosion from spilled electrolyte and released fumes. If the
batteries are located outdoors, the enclosure should be rainproof and have mesh screens to prevent insects and rodents from
entering. Before placing the batteries in the enclosure, cover the bottom with a layer of baking soda to neutralize any acid
spills.

3.4 Battery Connection

3.4.1 Connect your Inverter/Charger to your batteries using the following procedures:
• Connect DC Wiring: Though your Inverter/Charger is a high-efficiency converter of electricity, its rated output capacity is
limited by the length and gauge of the cabling running from the battery to the unit. Use the shortest length and largest
diameter cabling to provide maximum performance (see table below). Shorter and heavier gauge cabling reduces DC
voltage drop and allows for maximum transfer of current. Your Inverter/Charger is capable of delivering peak wattage at
up to 200% of its rated continuous wattage output for brief periods of time. Heavier gauge cabling should be used when
continuously operating heavy draw equipment under these conditions. Tighten your Inverter/Charger and battery terminals
to approximately 3.5 Newton-meters of torque to create an efficient connection and to prevent excessive heating at this
connection. Insufficient tightening of the terminals could void your warranty.
Maximum Recommended DC Cable Length
Maximum Distance From Battery to Inverter/
Charger
Wire Gauge (AWG)
Output
2
1000W
20 ft.
2000W
Do not use
Do not use
0
00 (2/0)
31 ft.
39 ft.
20 ft.
8