3. Communication protocol

This communication protocol supports the TOSHIBA Inverter Protocol and part of MODBUS-RTU
protocol.
Select the desired protocol from in the following communication protocol selection parameters
().
"Parameter Name , Communication Number. 0829"
Note : When using the extension panel (RKP001Z) and the parameter writer (PWU001Z), be certain
Data Range: 0, 1 (Initial value: 0)
0: TOSHIBA Inverter Protocol (Includes inter-drive communications)
1: MOUBUS-RTU protocol
* A parameter change is reflected when the inverter is reset, such as in power off.
to set F829="0" : TOSHIBA inverter protocol.
5
E6581222