8.2. Monitoring from the computer

This section explains how to monitor the operating status of the inverter from the computer.
Monitoring of the operation frequency from the computer (FE00, FD00)
Operation frequency (frequency immediately before the occurrence of a trip):
Operation frequency (current frequency): Communication Number FD00 (Minimum unit: 0.01 Hz)
Ex.: Monitoring of operation frequency (during 50 Hz operation) ... (1388H = 5000d, 5000 x 0.1 = 50
Hz)
Computer → Inverter
(RFD00)
Inverter operating status (FE01, FD01)
Operating status (status immediately before the occurrence of a trip):
Operating status (current status):
Table 2 Data construction of inverter operating status (FE00/FD00) (*: FD01 supports the VF-S11 and later models.)
Bit Specifications
0 Failure FL
1 Failure
2 Alarm
3 Reserved
4 Motor section (1 or 2)
(THR 2 selection)
5 PI control OFF
6 Acceleration/deceleration
pattern selection (1 or 2)
7 DC braking
8 Jog run
9 Forward/reverse run
10 Run/stop
11 Coast stop (ST=OFF)
12 Emergency stop
13 Standby ST=ON
14 Standby
15 Reserved
Inverter → Computer
(RFD001388)
CR
0
No output
Output in prog-
ress
Not tripped
Tripped
No alarm
Alarm issued
-
Motor 1 (THR 1) Motor 2 (THR 2)
PI control
PI control
permitted
prohibited
Acceleration/
Acceleration/
deceleration
deceleration
pattern 1 (AD 1)
pattern 2 (AD 2)
OFF
Forced DC
braking
OFF
Jog run
Forward run
Reverse run
Stop
Run
ST=ON
ST=OFF
Not emergency
Emergency stop
stop status
status
Start-up process
Standby
Start-up process
Standby
-
Communication Number FE00 (Minimum unit: 0.01 Hz)
CR
Communication Number FE01
Communication Number FD01
1
S7 S9
S11/nC1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
47
E6581222
Remarks
Trip statuses include 
and trip retention status.
THR1: PT=set value, vL, vb, Thr
THR2:PT=0, F170, F172, F173
AD1 :ACC, DEC,
AD2 :F500, F501
Standby: Initialization completed,
not failure stop status, not alarm
stop status (MOFF, LL forced
stop or forced stop due to a
momentary
power
failure),
ST=ON, and RUN=ON
Standby: Initialization completed,
not failure stop status, and not
alarm stop status (MOFF, LL
forced stop or forced stop due to
a momentary power failure)