SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (NiMh)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
GENERAL
This device is used indoors (ta 40 C) in
places where emergency luminaires are
needed. Each device must be permanently
connected to mains power supply. In normal
operation the battery is charging. In case of
a mains power supply failure, the device
enters emergency mode and the illumination
LED turns on. When the
supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 3.
Battery Charging
The
battery
charging
controlled. In this case, is achieved the
perfect battery maintenance , as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Battery Cut-off
The device in this operation when the mains
power supply fails and battery has lost its
energy. During this operation the device
enters the idle state and battery consumption
is negligible, in order to be protected from
deep discharge.
Page 1 from 6
GR-290/M
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
mains
power
is
completely
(for LED MODULE specifications see page 5)
GR-291/M
220-240V AC / 50-60Hz
4.3W / 4.7 VA
4.8V/1.2Ah
Deep discharge and overcharge protection
Charge, lamp fault, battery fault, TEST button
24 hours
1.5 hour
1 white power LED
300lm
IP40
5 to 40 C
Up to 95%
ABS/PC
Ø125 x 63 mm
439gr.
3 years (1 year for the battery)
Manual Test
This test can be done by pushing the test
button. The light source and the emergency
circuit of the device is monitored. The manual
test can be conducted only if the main power
supply and the battery is connected. During
this test period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
and emergency duration. The BATTERY
FAULT LED blinks during the measurement,
indicating this process to the user. This test is
conducted automatically every six months. In
order to be performed, the mains power
supply and the battery should be connected
and fully charged. If the battery is not fully
charged, the test is postponed until the
battery is completely charged. If during this
test, the autonomy is less than the nominal
then
the
battery
continuously
and
replaced.
GR-292/M
GR-293/M
3 hours
150lm
o
fault
led
turned
the
battery
must
923293003_09_006
on
be

Advertisement

loading

Summary of Contents for olympia electronics GR-290/M

  • Page 1 WEIGHT 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL Manual Test This device is used indoors (ta 40 C) in This test can be done by pushing the test places where emergency luminaires are button.
  • Page 2: Labeling Explanation

    Back Up Operation NOTE: LED= Light Emitting Diode The autonomous duration of battery during LABELING EXPLANATION: emergency mode is at least the one that is X: Self contained stated list technical 0: Non maintained (*) characteristics. During emergency mode, a A: Including test device light source test is also performed.
  • Page 3: Installation Instructions

    INSTALLATION INSTRUCTIONS Cable entry hole Initial installation 1. Untighten the screw but do not remove it and pull up the reflector. 2. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type 2x1mm² or any other type, at least equal to it’s mechanical and electrical properties). ATTENTION!! The cable must not be deformed in any way (This requirement is important to ensure the ΙΡ...
  • Page 4: Surface Mounting

    ATTENTION!! Especially for the GR-290/M and GR-292/M luminaire installation on the ceiling you must align the base with the indications on the luminaire’s base (Figure 5).
  • Page 5 GR-290/M, GR-292/M Corridor lighting LAMP BATT. CHARGE TEST LAMP BATT. FAULT CHARGE TEST FAULT ATTENTION!!! Lamp fault During installation follow this light direction. indication LED GR-291/M, GR-293/M Battery Battery charge fault indication indication Open area LAMP BATT. LAMP BATT. CHARGE...
  • Page 6: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-291/mGr-292/mGr-293/m