Multi-way wall switch vacancy sensor

Advertisement

4b.
Wiring one CH-250 and one RH-253 single pole momentary
switch for multi-way Manual-ON/OFF single load control.
• Connect the green or non-insulated (copper) GROUND wire in each wiring box
to the green terminal on each CH-250 and RH-253.
• Connect the NEUTRAL wire from the circuit and from the lamp (LOAD) to the
white wire on the CH-250.
• Connect the power wire from the circuit box (HOT) to one terminal of the
RH-253 single pole momentary wall switch and to the TRAVELER 1 wire.
• Connect the TRAVELER 1 wire coming from the RH-253 wiring box to the black
wire of the CH-250.
• Connect the lamp power (LOAD) to the red wire on the CH-250.
• Connect the TRAVELER 2 wire to the other side of the RH-253 single pole
momentary wall switch and to the yellow wire of the CH-250.
Yellow-> TRAVELER 2
to RH-253
Red -> LOAD
(power to lamp
or fan)
CH-250
Fig. 6: Step 4b. Sensor orientation and wire connections for 3-way operation
with an RH-253 momentary wall switch
To wire up to four RH-253 single pole momentary wall switches to one
CH-250, wire them in parallel as shown in the following wiring diagram.
Red
TOP
White
Black
Yellow
Ground
INDOOR USE ONLY
CH-250
Fig. 7: Step 4b. Reference wiring diagram for multi-way operation with RH-253
momentary wall switches (4 maximum)
5. Put all the new switches into their wall boxes.
Position the CH-250 switch(es) with the lens above the ON/OFF button (lens at
top, ON/OFF button at bottom). Use the captive screws on the mounting strap
to secure the switches to their wall boxes.
6. Restore power to the circuit.
Turn on the breaker or replace the fuse.
7. Make any necessary adjustments.
See the SENSOR ADJUSTMENT section for information.
8. Install cover plate.
Install industry standard decorator wall switch cover plate (not included).
IMPORTANT: The CH-250 must be installed in the
wiring wall box that connects to the load.
Black-> Traveler 1
power via RH-253
White ->
NEUTRAL
GROUND
TERMINAL
Neutral
Load
Ground
www.wattstopper.com
HOT (power from
Traveler 1 (Hot)
Traveler 2
Traveler 1
Traveler 2
RH-253
TRAVELER 1
circuit box)
GROUND
TERMINAL
RH-253
Hot
Traveler 1
Traveler 2
Ground
Traveler 1
Traveler 2
Ground
to CH-250
TRAVELER 2
to CH-250
RH-253