Assa Abloy Securitron AQD5 Series Installation Manual
Assa Abloy Securitron AQD5 Series Installation Manual

Assa Abloy Securitron AQD5 Series Installation Manual

Advertisement

Installation Manual
 Small – Light – Efficient – Clean Power
 Universal AC Input 90-250vac
 12vdc 5A/24vdc 3A Switch Selectable
 Smooth Linear Output Performance
 Input and Output Surge Protection
 Precise Battery Regulation for Wet, AGM,
and sealed Lead Acid Battery(s)
 Power Limited Output with Thermal
Protection
 Reverse Battery Protection
 AC , Trouble, and DC LED's
 Battery Online, No Drop or Switch Over
with AC Power Fail
 Quality Manufactured in the USA
 UL Listed Access Control & Burglar
Alarm systems
 Relay "C" Contacts Indicates AC Power Status
 Relay "C" Contacts Indicates Low Battery
Amber LED Indicates Power Normal
 Battery Cut-Off Relay Disconnects Battery(s)
when Depleted
 DC Output is Class II Power Limited
Ordering examples:
Supervised Power Supply/Charger module with
AQD5
a 14"x8.5"x3.5" Enclosure
-4F
AQD5 with one PDB-4F
-4C
AQD5 with one PDB-4C
-8F
AQD5 with one PDM-8-075-200
-8C
AQD5 with one PDM-8-075-090
-1R
AQD5 with one PDB-FT
-8C1R
AQD5 with one PDB-8C1R
-8F8R
AQD5 with one PDB-8F8R (Not UL Listed)
The AQD5 are heavy duty self contained, efficient,
clean, linear performance off-line switching power
supplies that are slide switch selectable between
12vdc at 5 Amps, and 24vdc at 3 Amps. Both have a
precision lead acid battery(s) charger that obtains
maximum battery life while providing a 12vdc or 24vdc
uninterruptible power supply for access control security
systems. The universal AC input allows these power
supplies to be powered anywhere in the world without
any alteration. The AQD5 has exceptional brown out
capability with operation down to 60vac. The AQD5
has an extensive filtering system that provides linear
output performance.
protected against Battery(s) reversal, shorting or
Securitron Magnalock Corporation
st
10027 S. 51
St., Ste. 102
Phoenix, AZ 85044
AQD5 Series 12/24 Power Supply/Charger
12VDC @ 5 Amps / 24VDC @ 3 Amps

Description / Instructions

The AQD5 is electronically
AQD5 12v/24v Series Power Supplies
Life Time Warranty
overloading.
The DC output is power limited, and
thermally protected. Each of these protective features
will self-restore. Before connecting load and battery(s),
slide 12v/24v selector switch to desired voltage.
Caution, damage can occur when switched with DC
output load. Confirm proper voltage before connecting
devices. The AQD5 is UL Listed and has the additional
supervisory features of a Battery disconnect relay when
battery(s) are depleted, a set of form "C" relay contacts
that indicates AC power failure, a set of form "C" relay
contacts to indicate low battery(s) and the DC Output is
Class II power limited. Depending on load, low battery
trouble indicates 50-75% battery capacity remaining.
Because the output of the AQD5 is Class II Power
Doc.# 500-33005 Rev B: Installation specifications subject to change without notice
leader
solutions.
Page 1 of 4
AQD5-8F
ASSA ABLOY, the global
in door opening
Phone: (800) MAGLOCK
customercare@securitron.com
www.Securitron.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Securitron AQD5 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Assa Abloy Securitron AQD5 Series

  • Page 1 50-75% battery capacity remaining. protected against Battery(s) reversal, shorting or Because the output of the AQD5 is Class II Power Doc.# 500-33005 Rev B: Installation specifications subject to change without notice ASSA ABLOY, the global leader in door opening Securitron Magnalock Corporation solutions.
  • Page 2 AQD5 12v/24v Series Power Supply continued Limited, all output devices connected to the AQD5 would automatically become class II Power Limited. AQD5 Specifications / Instructions AC Input: L, N, G - 3P Terminal block system with two depleted 12v 7AH batteries would take about Safety block with recessed hardware insulation that will 28 hours to re-charge.
  • Page 3 AQD5 12v/24v Series Power Supply continued Maintenance The power supply and stand by battery(s) should be tested at least once a year as follows: 1. Check LED’s for normal state. AC ON Green, Trouble Normal ON Green, DC ON Red. 2.
  • Page 4 AQD5 12v/24v Series Power Supply continued AQD5 Series Instructions: Doc.# 500-33005 Rev. B Page 4 of 4...

This manual is also suitable for:

Securitron aqd5-4fSecuritron aqd5-4cSecuritron aqd5-8fSecuritron aqd5-8cSecuritron aqd5-1rSecuritron aqd5-8c1r ... Show all

Table of Contents