Installation - Delta TP04P Series Instruction Sheet

Hide thumbs Also See for TP04P Series:
Table of Contents

Advertisement

Model
Point
TP04P-32TP1R
TP04P-16TP1R

Installation

Insert TP04P into the opening hole on the panel, and then tighten the screws. If it needs to be
mounted firmly, please use the mounting fixed supports and screws in the accessory package
which is packed with TP04P. Insert the hooks of the fixed supports into the fixing holes on the
back, and then tighten the screws. Please refer to figure 5 and figure 6 below for more
information.
(
The torque exerted on a screw should be 4.75 (kg-cm). Please tighten the screws
according to the specifications, otherwise the product may be damaged. If the fixed supports
are not installed well, Delta will not guarantee the waterproof rating.) The cover of the mounting
panel should be waterproof/dust proof or meet the related specifications (IP66/NEMA4).
Do not install TP04P in the following environment.
A location full of Airborne dust, metallic particles, oily smoke, corrosive or flammable
gases and liquids
High-temperature and humid environment
A location in which the product may be shocked and vibrated directly
Figure5
Wiring
use
1. Please
single-core cables or twin-core cables. The
diameters of the cables used should be within the range
between 16 AWG and 22 AWG (1.5mm). The torque applied
to the screw terminals should be 1.90 kg-cm (1.65 in-lbs).
Please use copper conducting wires. The temperature of the
copper conducting wires should be 60/75°C.
DO NOT w
2.
ire the empty terminal. DO NOT put the input signal cables and the output signal
cables in the same wiring.
3. DO NOT drop any tiny metallic conductor into the PLC while you are tightening screw and
wiring the PLC. After the wiring is complete, you have to ensure that heat can radiate from the
PLC.
Power Supply
The power input of TP04P is DC. When you operates TP04P, please note the following
points:
1. The power is connected to two terminals, 24 VDC and 0 V, and the range of power is
20.4 to 28.8 VDC. If the power voltage is less than 20.4VDC, TP04P will stop running,
all outputs will be Off, and the ERROR indicator will start to blink.
2. If a power failure lasts for less than 10 ms, the operation of TP04P will not stop.
Input
Type
16
DC
(Sink or Source)
8
Output
Point
Type
16
Relay
8
Figure 6
- 5 -
I/O Configuration
32TP1R
16TP1R
S/S0
C0
Y0
X0
Y1
X1
Y2
X2
X3
Y3
Y4
X4
S/S0
Y5
X5
X0
Y6
X6
X1
X7
Y7
X2
X3
X4
S/S1
C1
X5
Y10
X10
X6
Y11
X11
X7
Y12
X12
Y13
X13
Y14
X14
Y15
X15
Y16
X16
Y17
X17
22-16AWG
< 1.5mm
C0
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7