Model
Spec.
Display text
Program
upload/download
communication port
USB (COM1)
Extension
communication port
RS485 (COM2)
RS485 (COM3)
Battery cover
Monitoring method
Extension interface
Panel component
Alarm LED indicator
(Red)
Power LED indicator
(Green)
Display area
Numeric keys
Function keys
Enter key
Up/Down/Left/Right
keys

Electrical Specifications

Model
Spec.
CPU
Program memory
RAM of the system
Power supply voltage
Power consumption
Power protection
Insulation resistance
Noise immunity
Ground
Operating temperature
for hardware
5×8 dots: 38 characters × 8 rows
8×8 dots: 24 characters × 8 rows
Transmission method: Virtual communication port
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits, Parity: None/Odd/Even
Baud rate: 9,600 bps~115,200 bps
USB: USB (Type B) terminal
Asynchronous transmission method: RS-485
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits, Parity: None/Odd/Even
Baud rate: 9,600 bps~115,200 bps
RS-485: 8 PIN-removable terminal block
DC 3V battery
Download program to TP through virtual COM port
Slot for a program copy card
Status 1: When power is ON, LED will start to blink slowly
Status 2: When the user-defined conditions are met, LED will blink for
one second repeatedly along with an alarm sound.
When the power is connected to the product, LED will be ON.
LCM display area. It is used to display current program status.
0~9: They function as constants. Users can also define the keys by
themselves.
Users can define the keys by themselves
If the input value is correct, users can press the key. Users can define
the key in the user page.
Up: increase the value or move up one page.
Down: decrease the value or move down one page.
Left: Left direction key. Can be used to select the position of the
value.
Right: Right direction key. Can be used to select the position of the
value.
TP04P-16TP1R
LPC1787FBD208
1 MB-flash memory
64K Bytes
24VDC (-15% ~ 20%) (With counter-connection protection on the
polarity of DC input power)
3.2W
With counter-connection protection on the polarity of DC input
power
> 5 MΩ (all I/O point-to-ground insulation resistance: 500 VDC)
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O:
1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
The diameter of ground cannot be less than the diameter of the
power cable. (If severla PLCs are used, they should be grounded
directly.)
0°C~50°C: Relative humidity: 20%-90% RH (non-condensing)
TP04P series
8×12 dots: 24 characters × 5 rows
8×16 dots: 24 characters × 4 rows
Explanation
- 3 -
TP04P-32TP1R
5.2W