Please ensure to use TP series with Delta power supply module, DVPPS01, DVPPS02 or DVPPS05. EN TP04P is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating TP04P, or to prevent an accident from damaging TP04P, the control cabinet in which TP04P is installed should be equipped with a safeguard.
Page 3
Top View (Units: mm, [ ]: inch) (Units: mm, [ ]: inch) 162.2 [6.386] Figure5 162.7~164.0 [6.4055~6.4567] Figure 4 T hickness Range 0.5~5mm Function Specifications Model TP04P series Spec. PLC program capacity 8k steps Screen type/Display STN-LCD/Monochromatic color Driver Delta automation products Function/Numeric keys...
Page 4
RS (IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m The diameter of ground cannot be less than the diameter of the Ground power cable. (If several TP04P are used, they should be grounded directly.) Operating temperature 0°C~50°C: Relative humidity: 20%-90% RH (non-condensing)
Page 5
240VAC Inductive(cos 0.4) ψ 1,000 120VAC Inductive(cos =0.4) ψ 30VDC Inductive (t=40ms) Contact Figure 6 Current(A) Specifications for the analog input/output of TP04P-22XA1R/T Model Item Voltage input Current input Voltage output Current output Analog range ±10V ±20mA ±10V 0~20mA Digital conversion range ±2000...
Page 6
S/S1 Installation Insert TP04P into the opening hole on the panel, and then tighten the screws. If it needs to be mounted firmly, please use the mounting fixed supports and screws in the accessory package which is packed with TP04P. Insert the hooks of the fixed supports into the fixing holes on the back, and then tighten the screws.
Page 7
Off, and the ERROR indicator will start to blink. 2. If a power failure lasts for less than 10 ms, the operation of TP04P will not stop. However, if a power failure lasts for long, or the power voltage decreases, TP04P will stop running, and all outputs will be off.
Page 8
*2: Use a Zener diode (39V) in the PLC to protect the transistor output. When activating inductive load, we suggest you parallel connect a reverse current protection diode. Wiring Analog I/O and Temperature Sensor TP04P-22XA1R Analog Input Analog Output...
Page 9
2. To ensure communication quality, it is suggested that users should use double shielded twisted pair cables (20AWG) for wiring. Communication Connection TP04P may connect to a PC by using USB adaptor cable. Please use an AM/BM USB adaptor cable. Figure 21 ...