For roof top installation, be sure the structure will support obstruct the condenser air discharge outlet. the weight of the unit plus any field installed components. Unit must be installed on a level roof curb or appropriate Johnson Controls Unitary Products...
CONDENSATE DRAIN A condensate trap is required to be installed in the condensate drain. The plumbing must conform to local codes. Use a sealing Do not loosen compressor mounting bolts, except on rotary compressors. Johnson Controls Unitary Products...
REFER TO ELECTRICAL DATA REFER TO ELECTRICAL DATA TABLES TO SIZE THE DIS- TABLES TO SIZE THE DIS- CONNECT SWITCH, WIRING & CONNECT SWITCH, WIRING & OVERCURRENT PROTECTION OVERCURRENT PROTECTION FIGURE 3: TYPICAL FIELD WIRING DIAGRAM Johnson Controls Unitary Products...
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. Johnson Controls Unitary Products...
D M Coil Delta P vs’ Airflow 0.35 3.0 Ton 3.5 - 5.0 Ton 0.25 0.15 2.0 Ton 2.5 Ton 0.05 1000 1200 1400 1600 1800 2000 Airflow (CFM) FIGURE 4: COIL DELTA P VS AIRFLOW Johnson Controls Unitary Products...
Units may be installed on combustible floors made from wood or class A, B or C roof covering material. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet. FIGURE 5: DIMENSIONS AND CLEARANCES Johnson Controls Unitary Products...
“AUTO” position, the indoor motor will fan switch is in the “AUTO” position, the 24 volt “G” signal shut off after the appropriate time delay. Please refer to Tables 13 and 14 for more information. Johnson Controls Unitary Products...
HEATER BANK 2 (HTR 4, 5 & 6) ½ SEC. DELAY ON ”W2” HEATER BANK 1 (HTR 1, 2 & 3) 1 SECOND DELAY OFF HEATER BANK 1 (HTR 1, 2 & 3) 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF FAN 10 SECOND DELAY OFF Johnson Controls Unitary Products...
The wire number or color and terminal designations referred to may vary. Check the wiring label inside the control box access panel for the correct wiring. Johnson Controls Unitary Products...