MODEL DSV AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS Supersedes:145.29-IOM2 (812) Form 145.29-IOM2 (814) MODEL DSV60B-300B VERTICAL R-410A AIR CONDITIONING UNITS STYLE B Issue Date: August 25, 2014...
All wiring must be in accordance with published specifications and must be performed ONLY by qualified service personnel. Johnson Controls will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals.
FORM 145.29-IOM2 (814) CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continu- It is the responsibility of operating/service personnel as ous product improvement, the information contained in to the applicability of these documents to the this document is subject to change without notice.
C = Corrosion Protective Coating D = Stainless Steel Drain Pan F = Coated Coil w/ S-S Drain Pan Supply Air Discharge Configuration V= Top Vertical H=Front Horizontal * VFD OPTION AVAILABLE ONLY ON 10 TONS AND UP JOHNSON CONTROLS...
Repair any damage prior to installation to ensure safe operation. See Appendix section for unit dimensional drawings. Install thermostats, air supplies and returns so that each unit will operate only on individual unit control. To assure fast drainage of condensate run-off, unit JOHNSON CONTROLS...
Ensure that entire base is continuously - Charge circuit(s) to the value indicated on the unit supported. DO NOT support unit at nameplate section ‘Start-Up corner points only! Operation’. JOHNSON CONTROLS...
Example: Trapping a system up to 2” External static - Disconnect the evaporator motor high voltage pressure wires. Pull wiring into evaporator compartment. Remove bushing/clamp from A= (2”) + 1” C= A + B + 3/4” = 5-1/4” B= A/2 routing hole for evaporator motor wiring. JOHNSON CONTROLS...
VFD failure the evaporator fan will stop running ambient periods. (Installation oversize however unit compressors will continue to run until a condenser motor/drive, where applicable, may be low pressure safety trip is activated. considered in such cases.) JOHNSON CONTROLS...
5psi below the desired evaporator coil setpoint. The next step is to allow the pressure to be raised by the bypassed gas, the screw spring adjustment can be set until the HGBP valve closes at the desired set point. JOHNSON CONTROLS...
IN PART OR DISCLOSE ANY OF THE INFORMATION mounting to the top of evaporator for the 5-20 ton UPON IT TO OTHERS WITHOUT WRITTEN RELEASE BY VASE120B-UAS-IOM DWG NO: MATERIAL: SH. NO. 1 OF 2 JOHNSON CONTROL models. Discharge plenum is only compatible with top JOHNSON CONTROLS...
A routing hole is provided in the condenser corner panel, near the actuator mounting location, to allow installation of the plenum-rated cable between the motor and the control module. JOHNSON CONTROLS...
- Adjust drive belts to appropriate tension. Test run blower and observe operation for unusual For low voltage thermostat wiring, 18 gauge wire may sounds or vibration. be used for up to 50 feet lengths. Low voltage runs up to 125 feet require 16 gauge wire. JOHNSON CONTROLS...
Page 20
4) Once the pulley has been opened/closed the appropriate number of turns, replace the external key and tighten the adjustment setscrew. Proper torque is 110-130 in.-lbs. 5) Install drive belt and adjust motor mount to tension belt (see page 20: MAINTENANCE/SERVICE for further information). JOHNSON CONTROLS...
30 seconds. Additionally, the indoor blower Once the low-pressure switch has been proven has a delay of 10 seconds between operations. (closed during the 30-second monitoring period as described above), the microprocessor control board will continue to monitor the low-pressure limit switch JOHNSON CONTROLS...
Page 23
The microprocessor control incorporates features to minimize compressor wear and damage. An anti-short cycle delay (ASCD) is utilized to prevent short cycling of the compressor. Additionally, a minimum run time is imposed any time JOHNSON CONTROLS...
Compressor(s) locked out due to Economizer running (Free Cooling) * 13 Flashes Compressor Held Off due to Low Voltage 14 Flashes EEPROM Storage Failure No Power or Control Failure Note: Flash rates marked with * are NOT alarms. JOHNSON CONTROLS...
Check that the blower wheel is tight on the shaft, and that the hub set screws are properly torqued. LD13547 BELT TENSION ADJUSTMENT DEFLECTION FORCE VERSUS DRIVE BELT CROSS-SECTION JOHNSON CONTROLS...
CONNECTION CONDENSER DISCHARGE CONDENSER CONDENSER ACCESS PANEL INTAKE CONDENSER FAN DRIVE ACCESS PANEL 52.00 FRONT VIEW 47.13 2.44 1.75 DETAIL F SCALE 0.1 : 1 3/4" NPT DRAIN CONNECTION 2.25 47.50 NOTE: DIMENSION TOLERANCE IS 1/16" BACK VIEW JOHNSON CONTROLS...
Page 28
POWER SUPPLY CONDENSER CABLE ENTRANCE DISCHARGE CONDENSER LOW VOLTAGE BLOWER DRIVE CONNECTION ACCESS DOOR COMPRESSOR CONDENSER ACCESS PANEL INTAKE FRONT VIEW 64.63 2.20 3/4" NPT DRAIN CONNECTION FILTER 2.88 DETAIL A 66.50 NOTE: DIMENSION TOLERANCE IS 1/16" BACK VIEW JOHNSON CONTROLS...
Page 29
ACCESS PANEL DISCHARGE CABLE ENTRANCE LOW VOLTAGE CONNECTION CONDENSER BLOWER DRIVE CONDENSER ACCESS DOOR COMPRESSOR INTAKE ACCESS PANEL FRONT VIEW 64.63 2.20 3/4" NPT DRAIN CONNECTION FILTER 2.88 DETAIL A 66.50 NOTE: DIMENSION TOLERANCE IS 1/16" BACK VIEW JOHNSON CONTROLS...
Page 30
ELECTRICAL BOX ACCESS PANEL CONDENSER DISCHARGE LOW VOLTAGE CONDENSER CONNECTION BLOWER DRIVE ACCESS DOOR COMPRESSOR CONDENSER ACCESS PANEL INTAKE FRONT VIEW 76.13 1.97 3/4" NPT DRAIN CONNECTION FILTER 2.88 DETAIL A NOTE: DIMENSION TOLERANCE IS 1/16" 77.63 BACK VIEW JOHNSON CONTROLS...
Page 31
ACCESS PANEL DISCHARGE CABLE ENTRANCE LOW VOLTAGE CONDENSER CONNECTION BLOWER DRIVE ACCESS DOOR CONDENSER COMPRESSOR ACCESS PANEL INTAKE FRONT VIEW 76.13 1.97 3/4" NPT DRAIN CONNECTION FILTER 2.88 DETAIL A 77.63 NOTE: DIMENSION TOLERANCE IS 1/16" BACK VIEW JOHNSON CONTROLS...
Page 32
POWER SUPPLY DISCHARGE CABLE ENTRANCE LOW VOLTAGE CONDENSER CONNECTION CONDENSER BLOWER DRIVE COMPRESSOR INTAKE ACCESS PANEL ACCESS PANEL FRONT VIEW 84.13 1.97 3/4" NPT DRAIN CONNECTION FILTER 1.88 DETAIL A 3.19 85.63 NOTE: DIMENSION TOLERANCE IS 1/16" BACK VIEW JOHNSON CONTROLS...
Page 33
POWER SUPPLY DISCHARGE CABLE ENTRANCE LOW VOLTAGE CONNECTION COMPRESSOR CONDENSER CONDENSER ACCESS PANEL BLOWER DRIVE INTAKE ACCESS PANEL FRONT VIEW 84.13 1.97 3/4" NPT DRAIN CONNECTION FILTER 1.88 DETAIL A 3.20 85.63 NOTE: DIMENSION TOLERANCE IS 1/16" BACK VIEW JOHNSON CONTROLS...
Page 34
CONDENSER CABLE ENTRANCE DISCHARGE LOW VOLTAGE CONNECTION CONDENSER BLOWER DRIVE CONDENSER COMPRESSOR ACCESS DOOR INTAKE ACCESS PANEL FRONT VIEW 102.13 2.00 3/4" NPT DRAIN CONNECTION FILTER 2.88 DETAIL A NOTE: DIMENSION TOLERANCE IS 1/16" 3.19 103.63 BACK VIEW JOHNSON CONTROLS...
Page 35
LOW VOLTAGE CONDENSER CONNECTION BLOWER DRIVE ACCESS D OOR COMPRESSOR CONDENSER AC CESS PAN EL INTAKE FRONT VIEW 102.13 2.00 3/4" NPT DR AIN CONNECTION FILTER 2.88 DETAIL A 3.19 103.63 NOTE: DIMENSION TOLERANCE IS 1/16" BACK VIEW JOHNSON CONTROLS...
20 TON A/C VERTICAL UNIT FORM 145.29-IOM2 (814) SERVICE CLEARANCE REAR RETURN, FRONT DISCHARGE APPENDIX B: TYPICAL SERVICE CLEARANCES 24 In. Side 42 In. Front ELECTRICAL BOX ACCESS PANEL COMPRESSOR ACCESS PANEL JOHNSON CONTROLS...
Do not use an R-22 TXV. If a TXV is to be used, it must be an R-410A TXV. Never open system to atmosphere when under vacuum. If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace filter driers. JOHNSON CONTROLS...