BACnet Gateway for VRF System
5.3.21 IU_rr_uu_AutoTempHiLim_Setting (Analog Output Object Type)
Set temperature upper limit values when Auto Mode is active can be commanded for indoor unit.
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Update_Interval
Units
Min_Pres_Value
Max_Pres_Value
Resolution
COV_Increment
Priority_Array
Relinquish_Default
Time_Delay
Notification_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Event_Message_Texts
Event_Message_Texts_Config
Event_Detection_Enable
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
REAL
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetEngineeringUnits
REAL
REAL
REAL
REAL
BACnetPriorityArray
Unsigned
Unsigned
Unsigned
REAL
REAL
REAL
BACnetLimitEnable
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
BACnetArray[3] of
CharacterString
BACnetArray[3] of
CharacterString
BOOLEAN
Copyright© 2021 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.4.0 eng
Value
(Analog Output, 12rruu)
"IU_rr_uu_AutoTempHiLim_Setting"
ANALOG_OUTPUT (1)
18 ~ 30(°C) // 64 ~ 88(°F)
-
-
{FALSE, FALSE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0)
FALSE
-
Degrees Celsius (62) // Fahrenheit (64)
-
-
-
0
BACnetPriorityArray
26
-
-
-
-
-
-
-
-
-
-
-
-
-
UTY-
ASHRAE
VBGX
R
R
R
R
R
R
W
W
O
-
O
-
R
R
R
R
O
R
R
R
O
-
R
R
O
-
O
-
O
-
O
R
R
R
R
R
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
-
O
-
O
R*
65/159