BACnet Gateway for VRF System
5.3.12 IU_rr_uu_SpaceTemp_Status (Analog Input Object Type)
Indoor unit surrounding temperature status can be monitored.
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Update_Interval
Units
Min_Pres_Value
Max_Pres_Value
Resolution
COV_Increment
Time_Delay
Notification_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Event_Message_Texts
Event_Message_Texts_Config
Event_Detection_Enable
Event_Algorithm_Inhibit_Ref
Event_Algorithm_Inhibit
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
REAL
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetEngineeringUnits
REAL
REAL
REAL
REAL
Unsigned
Unsigned
REAL
REAL
REAL
BACnetLimitEnable
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
BACnetArray[3] of
CharacterString
BACnetArray[3] of
CharacterString
BOOLEAN
BACnetObjectPropertyRefer
ence
BOOLEAN
Copyright© 2021 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.4.0 eng
Value
(Analog Input, 11rruu)
"IU_rr_uu_SpaceTemp_Status"
ANALOG_INPUT (0)
0 ~ 63.5(°C) // 30 ~ 148(°F)
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
FALSE
-
Degrees Celsius (62) // Fahrenheit (64)
-
-
-
0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
UTY-
ASHRAE
VBGX
R
R
R
R
R
R
R
R
O
-
O
-
R
R
R
R
O
R
R
R
O
-
R
R
O
-
O
-
O
-
O
R
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
-
O
-
O
R*
O
-
O
-
46/159