Specifications Of Electrical Parts - Toshiba RAS-10SAV-A Service Manual

Split wall type
Table of Contents

Advertisement

6. SPECIFICATION OF ELECTRICAL PARTS
6-1. Indoor Unit
No.
Parts name
1
Fan motor (for indoor)
2
Thermo. sensor (TA-sensor)
3
Micro power module (T101)
4
Microcontroller unit (IC81)
5
Heat exchanger sensor
(TC-sensor)
6
Line filter (L01)
7
Diode (D01,D02,D03 and D04)
8
Capacitor (C03)
9
Fuse (F01)
10
Regulator IC (IC12)
11
Varistor (R21)
12
Louver motor
Type
AFS-220-20-4AR
µRM1260V
PD780076GK-703-9ET-A
SS11V-R06270
S5688J
EKMH401VSN470MP20S
FJL250V3.15A
S7805PIC
TNR10V471K-T8
24BYJ48
– 18 –
FILE NO. SVM-07008
Specifications
AC Motor with 145°C thermo fuse
10 k at 25 C
10 k at 25 C
27 m H, AC 0.6A
47µF, 400V
3.15A, 250 V
5VDC, 0.5A
470V
DC 12V

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents