RL-378 Optional I/O Expansion Board with 240V Relays, Continued.
Remote Alarm Inputs
There are 7 alarm inputs on the RL-378. Each can be individually DIP switch selected for
either digital or analogue mode. In digital mode, standard open circuit and closed circuit
conditions are expected. In the analogue mode, a normal input state requires a total
loop resistance of 10KΩ. The DIP switch settings are as follows.
The MAXPRO-Net software allows these remote alarm inputs to be utilized in exactly the
same way, as are those from a RD-400 alarm input card.
The alarm test facility (SW1-8) automatically echoes the current alarm input state back
out the relay outputs. Using the output LEDs the alarm input can be locally tested and
verified. Alarm inputs 1→7 are echoed to relay outputs 1→7. The tamper input on the
RD-378 is echoed to relay output 8. Note that this test facility should be disabled during
normal system operation.
Manual Iris Control
This output provides +ve and –ve voltages for manual iris control. This output is from
PL12 on the RL-378 board. There are 2 links associated with this output that select
between 6 volt or 12 volt iris motors.
These link positions do not affect the zoom or focus motor voltages.
Rev. C
DIPSWITCH SETTINGS
SW1
DESCRIPTION
1
Alarm 1 mode
2
Alarm 2 mode
3
Alarm 3 mode
4
Alarm 4 mode
5
Alarm 5 mode
6
Alarm 6 mode
7
Alarm 7 mode
8
Alarm Test
LK1 and LK2 both off for 12V iris motors.
LK1 and LK2 both on for 6V iris motors.
ON
OFF
Analogue
Digital
Analogue
Digital
Analogue
Digital
Analogue
Digital
Analogue
Digital
Analogue
Digital
Analogue
Digital
Test
Normal
7.11-15
HMXMU001018