Siemens SIMATIC ET 200SP Manual page 28

Technology module tm count 1x24v
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Configuring/address space
4.4 Control and feedback interface
Offset to the start
Parameter
address
Byte 8
LD_SLOT_1*
Byte 9
EN_CAPTURE
EN_SYNC_DN
EN_SYNC_UP
SET_DQ1
SET_DQ0
TM_CTRL_DQ1
TM_CTRL_DQ0
SW_GATE
Byte 10
SET_DIR
RES_EVENT
RES_ERROR
Byte 11
*
If values are loaded simultaneously via LD_SLOT_0 and LD_SLOT_1, the first value is taken internally from Slot 0 and
then the value from Slot 1 is taken. This may lead to unexpected intermediate states.
28
Meaning
Specifies the significance of the value in Slot 1
Bit 7
Bit 6
Bit 5
0
0
0
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
to
1
1
1
Bit 7: Capture function enable
Bit 6: Enable synchronization down
Bit 5: Enable synchronization up
Bit 4: Set DQ1
Bit 3: Set DQ0
Bit 2: Enable technological function DQ1
Bit 1: Enable technological function DQ0
Bit 0: Software gate
Bit 7: Count direction (for encoders without direction signal)
Bits 2 to 6: Reserve; bits must be set to 0
Bit 1: Reset of saved events
Bit 0: Reset of saved error states
Bits 0 to 7: Reserve; bits must be set to 0
Bit 4
0
No action, idle
1
Load counter value
0
Reserve
1
Load start value
0
Load comparison value 0
1
Load comparison value 1
0
Load low counting limit
1
Load high counting limit
0
Reserve
1
Technology Module TM Count 1x24V (6ES7138‑6AA00‑0BA0)
Manual, 10/2013, A5E33002339-AA

Advertisement

Table of Contents
loading

Table of Contents