Wiring
3.1 Pin assignment
Input filters for digital inputs
To suppress interferences, you can configure an input filter for the digital inputs.
You can specify the following values for the filter time:
● None
● 0.05 ms
● 0.1 ms (default)
● 0.4 ms
● 0.8 ms
● 1.6 ms
● 3.2 ms
● 12.8 ms
● 20 ms
Note
If you select the "None" or "0.05 ms" option, you have to use shielded cables for connection
of the digital inputs.
Digital outputs DQ0 and DQ1
There are two digital outputs. The two digital outputs DQ0 and DQ1 can be
activated/switched directly by the specified comparison values or by the user program.
The digital outputs are not isolated from each other.
The digital outputs are 24 V sourcing outputs in reference to M and can carry a rated load
current of 0.5 A. They are protected from overload and short-circuit.
Note
Relays and contactors can be connected direct without external circuitry. You can find
information on the maximum possible operating frequencies and the inductive loads at the
digital outputs in the section Technical specifications (Page 41).
22
Technology Module TM Count 1x24V (6ES7138‑6AA00‑0BA0)
Manual, 10/2013, A5E33002339-AA