Daikin VRV 5 BS4A14AJV1B Manual page 99

Branch selector unit
Hide thumbs Also See for VRV 5 BS4A14AJV1B:
Table of Contents

Advertisement

BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
This setting is only to be used during the test run of the BS unit when a ventilated
enclosure is used as a safety measure of the BS unit and an external alarm is added
as an additional measure. During the BS unit test run, which is started by setting
[2-3] to "1", the external fan and external alarm are both active. To disable the
external alarm during the airflow rate measurements, change setting [2-10] to "1".
Once the BS unit test run is finished (setting [2-3] changed to "0"), setting [2-10]
automatically returns to its default value "0".
This setting only has to be configured on the leftmost main PCB (A1P) of the BS
unit.
[2-10]
0 (default)
1
External alarm output forced OFF
Disable
Enable
17
Configuration
|
Installer and user reference guide
99

Advertisement

Table of Contents
loading

Table of Contents