Daikin VRV 5 BS4A14AJV1B Manual page 62

Branch selector unit
Hide thumbs Also See for VRV 5 BS4A14AJV1B:
Table of Contents

Advertisement

14
|
Unit installation
Installer and user reference guide
62
a Suspension bolt pitch (length): 513 mm
b Suspension bolt pitch (width):
630 mm (BS4A)
1030 mm (BS6~8A)
1430 mm (BS10~12A)
2 Install a nut, 2 washers and a double nut onto each suspension bolt. Leave
enough space for maneuvering with the unit between the nut and double nut.
3 Position the unit by hooking the hanger brackets of the unit around the
suspension bolts, in between the 2 washers.
a Nut (field supply)
b Washer (field supply)
c Hanger bracket
d Double nut (field supply)
a Ceiling slab
b Anchor bolt
c Long nut or turnbuckle
d Suspension bolt
e BS unit
4 Secure the unit by tightening the nut and double nut.
5 Level the unit at all 4 corners by turning the double nuts, the long nuts or the
turnbuckles. Use a level or water-filled vinyl tube to measure if the unit hangs
level. A deviation of maximum 1 degree is allowed in the direction of the drain
socket and away from the switch box.
NOTICE
If the unit is installed at a bigger angle than allowed, water may drip from the unit.
b
a
a
b
c
b
d
a
b
c
d
e
BS4~12A14AJV1B