2 Attach the provided M5 nuts to the rack. Use the provided M5 screws to firmly
install the Plug-in manual bypass on the rack. Ensure that the screws are tightly
fixed.
6.4. Battery/ Battery Pack Replacement
1. Shut down the UPS and switch off the AC power source before replacing the
battery or battery pack.
2. A battery can present a risk of electric shock and high short-circuit current.
3. Servicing of batteries and battery packs must be performed or supervised
by qualified service personnel who are familiar with batteries, battery packs and
the required precautions. Keep unauthorized personnel away from batteries and
battery packs.
Replace the battery/ battery pack by following the procedures below.
1 Remove the screws and remove the battery pack's front bezel
2 Disconnect the battery terminals
3 Use the insulated screwdriver to remove the screws from the protective cover
located in front of the battery
42
EN
Plug-in manual bypass
M5 NUT x 2
(Left: 1 & Right:1)
2
.
3
.
M5
screw x 2
(Left: 1 & Right:1)
NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
Plug-in manual bypass
1
.