Function Setting Procedure Using Reset Button; Control Box Reset (Using Built-In Button); Control Box Reset (Via Remote Connection); Maintenance - Riello RX 70 S/PV Installation, Use And Maintenance Instructions

Pre-mixed gas burner
Table of Contents

Advertisement

Available languages

Available languages

4.12

FUNCTION SETTING PROCEDURE USING RESET BUTTON

Control box function
control box
Reset
Vi s u a l d i a g n o s t ic s o f l o c k o u t
causes (5.1)
Post-purging (4.9)
Resetting set functions
Resetting operating parameters
4.13

CONTROL BOX RESET (USING BUILT-IN BUTTON)

To reset the control box, proceed as follows:
Press and hold the reset button down for between 1 and 2 seconds.
If the burner does not restart, you must make sure the limit thermostat (TL) is closed.
Warning:
If you hold the reset button down for more than 2 seconds, the control box enters visual diagnostic mode
and the signalling LED begins to blink (see paragraph 5.1, page 16).
To reset the control box, you must press the reset button again.
4.14

CONTROL BOX RESET (VIA REMOTE CONNECTION)

Socket XP7 has an input B4 provided for the control box's remote resetting.
5.

MAINTENANCE

Before cleaning or performing checks, switch off the burner's power supply with the system's master
switch and close the gas shutoff valve.
The burner requires periodic maintenance carried out by a qualified and authorised technician in conformity
with legislation and local standards.
Scheduled maintenance is vital for the smooth operation of the burner; it avoids waste of fuel and reduces pol-
lutant emissions into the atmosphere.
FUNDAMENTAL OPERATIONS TO BE CARRIED OUT ARE AS FOLLOWS:
Make sure the air intake areas and ducts taking the flue gases away do not feature any obstructions or
restrictions.
Electrical wiring
Check that the burner and gas train electrical connections are correct.
Gas leaks
Make sure there are no gas leaks in the following areas:
- on the meter-burner pipework
- on the mixer/valve connection
- on the burner fastening flange where the seal is fitted.
Combustion head
Inspect the combustion head and make sure the fabric is undamaged and does not features large or
deep holes or corroded areas. Also make sure that no parts have warped as a result of high
temperature.
Electrode unit
Make sure neither the electrodes nor probe feature marked warping or oxidation on surfaces. Make sure
distances are still in line with those indicated in fig. 4, readjusting to the right values where necessary.
Where necessary, remove oxide from the surface of the probe with abrasive paper.
3350
Action with the reset
button
1 to 2 seconds
3 seconds
5 seconds then press
once = 1 minute
5 seconds
5 seconds
15 GB
Possible Reset button
use status
After control box lockout
After control box lockout
W it h limit thermostat (TL) not
switched (burner off)
W it h limit thermostat (TL) not
switched (burner off)
With limit thermostat (TL) switched
during pre-purging

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

901 t3790100

Table of Contents