Transport And Handling; Packing; Transport; By Receiving Inspection - ABB SafeRing XT Installation And Operating Instructions Manual

Table of Contents

Advertisement

12
SAFERING XT/SAFEPLUS XT

3. Transport and handling

The units are delivered from the factory ready for
installation.

3.1 Packing

The SafeRing XT/SafePlus XT is normally delivered packed
from the factory. For longer transportation distances,
protective measures such as wooden corners, plastic film
etc., are used. This should be removed, when the RMU is at
site and before installation.

3.1.2 Transport

During transport of packed RMU is to be firmly fixed to the
truck with help of Belts to avoid any damage in transit.
Once Unpacked, SafeRing XT/SafePlus XT is fitted with
lifting lugs but can also be moved on a pallet with a forklift
truck.
Refer the following lifting options available using overhead
cranes or Forklifts for RMU movement.
Figure 3.1
Figure 3.2
RMU lifting front view
RMU lifting Isometric view
Figure 3.3
RMU+Metering coupled switchgear lifting
Figure 3.4
RMU lifting using Forklift
Caution
The units with heavy top, so please handle with care.
Proper belting must be used while transporting on
forklifts to avoid toppling of the unit. No roller/any other
method should be used for transportation of the
switchgear.
NOTE
Use only approved slings when lifting. Maximum angle
on lifting lugs is set to 90°. Compulsorily use all 4 top
lifting lugs.

3.1.3 By receiving inspection

Upon receiving the SafeRing XT/SafePlus XT check that
the delivered equipment has not been damaged during
transport. If any such damage has occurred, a claim must be
submitted to the carrier immediately.
After unpacking, the following must be checked:
1. Operating handle
one piece is included, normally
A
fixed on inside of main door.
2. Check that the pointer on the pressure indicator
the green area.
3. Carry out a function test on the mechanical parts.
4. Visual check of the switchgear. Any faults or omissions
must be reported immediately to the supplier.
5. Loose materials sent along with RMU must be stored
indoor to avoid corrosion/damage to these items.
Figure 3.5
Operating handle
, is in
B
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Safeplus xt

Table of Contents