8. Cable compartment

8.1 Standard Arc proof cable compartment

8.1.1. To Remove cable cover:

1. Unlock the front padlock and then open the main door.
Figure 8.1
Unlocking of front door
2. Ensure the Switch-Disconnector/Disconnector of
respective module is in Earth position.
CAUTION!
Refer Chapter 1 for Safety guidelines
Note:
1. Cable door can't be open when Disconnector or Switch
disconnector is in Off or On condition.
2. Cable door Can be opened only when particular module
earth switch is in On position.
3. Once the door is open Disconnector or Switch
disconnector operation access is blocked (Refer
Chapter 19 (Cable testing) and Chapter 8.1.3 (Defeat
interlock) for more information)