Nice Flood-Control Instructions And Warnings For Installation And Use page 10

Wireless water leak detector
Table of Contents

Advertisement

Parameter:
63. Temperature indication using LED visual indicator
Description:
Parameter determines visual indicator's operation. Setting to 0 turns the temperature LED indication off, saving
battery life.
Available settings:
0 - visual indicator does not indicate the temperature
1 - visual indicator indicates the temperature (blink) every Temperature Measurement Interval (parameter 10, con-
stant current and battery) and Wake Up Interval (battery mode)
2 - visual indicator indicates the temperature continuously, only in constant power mode
Default setting:
2
Parameter:
73. Temperature measurement compensation
Description:
Parameter stores a temperature value to be added to or deducted from the current temperature measured by
internal temperature sensor in order to compensate the difference between air temperature and temperature at
the floor level.
Available settings:
-10 000 to +10 000
Default setting:
0 (0.00°C)
Parameter:
74. Alarm frame sent to 1st and 4th Association Group activation (MOVEMENT_TAMPER / BUTTON_TAMPER)
Description:
The device is able to report tamper alarms resulting from sensor's tilt/movement or TMP button state change (e.g.
taking off the top cover).
Available settings:
0 - tamper alarms inactive
1 - button tamper alarm active
2 - movement tamper alarm active
3 - button and movement tampers alarm active
Default setting:
2
Parameter:
75. Alarms signalization duration
Description:
The device is capable of automatically turning off alarm signalization after a certain amount of time. Long lasting
alarm may reduce battery life, when constantly signalized. The parameter determines time after which alarm will
become "quiet" - still active but the device will go into battery saving mode. Visual or acoustic alarm will be reacti-
vated after time specified in the parameter 76. When alarm status ceases, alarm will be turned off immediately.
Available settings:
0 - alarms active indefinitely
1-65535 - time in seconds
Default setting:
0
Parameter:
76. Alarm signalization reactivation period
Description:
Parameter determines a time period after which an alarm will be turned back on (in case it was turned off by pa-
rameter 75 setting). It will also resend commands to 2nd and 3rd association groups as if the alarm was detected
again.
Available settings:
0 - alarm reactivation inactive
1-65535 - time in seconds
Default setting:
0
Parameter:
77. Flood sensor functionality turned off
Description:
Allows to turn off the internal flood sensor. Tamper and built in temperature sensor will remain active.
Available settings:
0 - Default flood sensor operation (flood detection, reactions)
1 - Built-in flood sensor TURNED OFF (does not change its state in the main controller, does not send alarm
notifications nor turn on/off commands to 2nd/3rd association groups with flood state changes. Always visible in
the main controller as turned off)
Default setting:
0
Parameter:
78. Associations in Z-Wave network security mode
Description:
This parameter defines how commands are sent in specified association groups: as secure or non-secure. Pa-
rameter is active only in Z-Wave network security mode. It does not apply to 1st "Lifeline "group.
Available settings:
0 - none of the groups sent as secure
1 - 2nd group "Control" sent as secure
2 - 3rd group "Alarm" sent as secure
4 - 4th group „Tamper" sent as secure
Default setting:
7
Parameter size:
1 [byte]
Parameter size:
2 [bytes]
Parameter size:
1 [byte]
Parameter size:
4 [bytes]
Parameter size:
4 [bytes]
Parameter size:
1 [byte]
Parameter size:
1 [byte]