TECHTOP TD350 Product Manual page 96

Hide thumbs Also See for TD350:
Table of Contents

Advertisement

TD350 Series VFD
Function
code
Upper limit frequency of
P05.41
Corresponding setting of
P05.42
upper limit frequency of
HDIA frequency input filter
P05.43
HDIB high-speed pulse input
P05.44
Lower limit frequency of
P05.45
Corresponding setting of
P05.46
lower limit frequency of HDIB
Upper limit frequency of
P05.47
Corresponding setting of
P05.48
upper limit frequency of
HDIB frequency input filter
P05.49
P05.50
AI1 input signal type
5.5.10 Analog output
The TD350 series VFD carries one analog output terminal (0–10V/0–20mA) and one high-speed
pulse output terminal. Analog output signals can be filtered separately, and the proportional relation
can be adjusted by setting the max. value, min. value, and the percentage of their corresponding
output. Analog output signal can output motor speed, output frequency, output current, motor torque
and motor power at a certain proportion.
Name
HDIA
HDIA
time
function selection
HDIB
HDIB
HDIB
time
Detailed parameter description
P05.39 –50.000KHz
-100.0%–100.0%
0.000s–10.000s
0: Set input via frequency
1: Reserved
2: Input via encoder, used in
combination with HDIA
0.000 KHz – P05.47
-100.0%–100.0%
P05.45 –50.000KHz
-100.0%–100.0%
0.000s–10.000s
0–1
0: Voltage type
1: Current type
-91-
Basic operation instructions
Default
value
50.000KHz
100.0%
0.030s
0
0.000KHz
0.0%
50.000KHz
100.0%
0.030s
0

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TD350 and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Topdrive 350 seriesTd350 series

Table of Contents

Save PDF