TD350 Series VFD
Function
Name
code
Current setting in
IF mode for
P04.41
asynchronous
motor 1
Proportional
coefficient in IF
P04.42
mode for
asynchronous
motor 1
Integral
coefficient in IF
P04.43
mode for
asynchronous
motor 1
Frequency
threshold for
switching off IF
P04.44
mode for
asynchronous
motor 1
Enable/disable IF
mode for
P04.45
asynchronous
motor 2
Current setting in
IF mode for
P04.46
asynchronous
motor 2
Proportional
coefficient in IF
P04.47
mode for
asynchronous
motor 2
Detailed parameter description
When IF control is adopted for asynchronous motor
1, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0–200.0%
When IF control is adopted for asynchronous motor
1, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0–5000
When IF control is adopted for asynchronous motor
1, this parameter is used to set the integral
coefficient of the output current closed-loop control.
Setting range: 0–5000
When IF control is adopted for asynchronous motor
1, this parameter is used to set the frequency
threshold for switching off the output current
closed-loop control. When the frequency is lower
than the value of this parameter, the current
closed-loop control in the IF control mode is
enabled; and when the frequency is higher than
that, the current closed-loop control in the IF control
mode is disabled.
Setting range: 0.00–20.00 Hz
0: Disabled
1: Enabled
When IF control is adopted for asynchronous motor
2, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0–200.0%
When IF control is adopted for asynchronous motor
2, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0–5000
-157-
Function parameter list
Default
Modify
value
○
120.0%
○
650
○
350
10.00H
○
z
◎
0
○
120.0%
○
650
Need help?