Communication Option

Software Installation

2. Press and release the SET/ENT button to access the six parameters specific to
communication option.
Parameter Code
Communications Setup Parameters
PSL
Adr
bPs
Pr 1
StP
DLn
Software Installation
1. Load the SpecView software onto the PC hard drive, using the disks provided.
2. Run the software. (If you have purchased the SpecView Plus Communication
Software with the copy protection key, Skip step 3.)
3. If you do not have a copy protection key. a "SpecView" window opens with the
message, "Problem with Dongle: 'Dongle' (Copy Protection Key) not detected
on parallel port." Click the OK button to acknowledge the message. Without the
copy protection key, this diagnostic/sampler software has a 20-minute time
limit on each run. If the message "demo version of SpecView has stopped
communicating - value are frozen" appears before the communication
diagnostics/sampler are finished, close the software and reopen it for another
20-minute segment.
4. When the "Configuration Founds.." windows opens, click on the "Test Comms
for New Config." Button.
5. The "Input Required.." window then opens. Enter a new Config. Name (up to 8
characters with no spaces) or accept the "DEFAULT" name. Click OK.
6. The "Port and Protocol" window opens next. On the "COM1:" line (if the COM1
port is the serial port used to connect to the port controller) select the pulldown
menu from protocol column. Highlight. "*Yokogawa 100" or "100 Series" Need
to identify the proper/accurate selection from the current Communications
Software for controller mode UT150.
7. Select the pulldown menu from the Baud Rate column. Highlight "9600".Click
on the "Start Scan" button.
8. The SpecView program scans all 99 possible controller addresses and places
a representative "instrument view" of the temperature controller on the PC
7-2
Table 3. UT150 Communications Parameters
Factory Set Value
0
1
9600
EVN
1
8
Description
Protocol selection
Controller address
Baud rate
Parity (even)
Stop bit
Data length
Thermo Scientific