Toshiba DeviceNet nv Series Instruction Manual page 50

Table of Contents

Advertisement

Chapter 3 Install and Wiring
Node
3
1.1A
a) Section 1 current consumption = 1.1A + 1.25A = 2.35A
a') Section 2 current consumption = 0.5A + 0.25A + 0.25A + 0.85A = 1.85A
b) Section 1 total extension = 100 m
b') Section 2 total extension = 140 m
c) From Figure 3-5, the maximum current that can flow through the cable in section 1 = about 2.93 A
c') From Figure 3-5, the maximum current that can flow through the cable in section 2 = about 2.19 A (calculated
by linear approximation 100 to 150 m)
d) Since the total current consumption of both sections 1 and 2 < maximum current, power can be supplied to
all nodes with a single power supply central connection.
e) Use a network power supply with a rated current of 4.2 A or more.
(Select a product with sufficient margin in consideration of usage conditions, etc.)
34
6F8C1686
Section 1
100m
V+
Node
Power
2
tap
1.25A
V-
Network
power supply
Figure 3-10 Example of overload solutions
Section 2
140m
Node
Node
Node
1
4
0.5A
0.25A
Node
5
6
0.25A
0.85A