ABB ACS880 User Manual page 42

Safely-limited speed without the encoder interface (option +q966) for multidrives
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

42 Parameter settings
Index
Name
SARx.21
SAR1 min ramp time
to zero
SARx.22
SAR1 max ramp time
to zero
I/O settings
SAFEIO.34
DI X113:2 diag pulse
on/ off
SAFEIO.38
DI X114:2 diag pulse
on/ off
SAFEIO.56
DO X114:7 diag
pulse on/off
SAFEIO.74
DO X114:7 logic
state
Example value
Description
1000 ms
Sets the minimum ramp time for the SAR1
ramp monitoring.
Time monitoring: This value has no effect
in the operation.
Ramp monitoring: Sets the minimum decel-
eration time for the emergency stop. Adjust
the default value when necessary.
Note: With value 0 ms, the ramp is not
monitored.
3000 ms
Sets the maximum ramp time for the SAR1
ramp monitoring.
Time monitoring: This value has no effect
in the operation.
Ramp monitoring: Sets the maximum decel-
eration time for the emergency stop. Adjust
the default value when necessary.
Off
Sets the diagnostic pulse of digital input
X113:2 on or off.
Off: The input monitors that it does not re-
ceive test pulses.
Off
Sets the diagnostic pulse of digital input
X114:2 on or off.
Off: The input monitors that it does not re-
ceive test pulses.
On
Sets the diagnostic pulse of digital output
X114:7 on or off.
On: The output monitors that it receives test
pulses.
Active high
Sets the logic state of digital output X114:7.
Active high: The digital output is on when
the indicated signal is active.
For option +Q966, ABB has configured the
SLS indication signal to this digital output at
the factory. Make sure that this value corres-
ponds to the actual wiring. Refer to the cir-
cuit diagrams of the delivery.