ABB ACS880 User Manual page 19

Safely-limited speed without the encoder interface (option +q966) for multidrives
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

1.
The user or a PLC de-energizes the applicable digital inputs of the FSO module. This
activates the SLS request. The FSO module starts a counter for time (B).
2.
After the safety function response time (A), the inverter unit starts to decelerate the
motor according to the user-defined deceleration ramp. The FSO module starts SLS
monitoring and energizes the digital output that indicates the SLS status when the motor
speed is in the middle of the SLS1 trip limit and the SLS1 limit.
3.
The actual motor speed reaches the SLS1 limit positive. The inverter unit limits the
motor speed reference so that the motor speed stays at or below the SLS1 limit positive.
The FSO module monitors the actual motor speed. If the motor speed goes above the
SLS1 trip limit positive (D), the FSO module activates the SSE function (refer to section
SLS with speed below the monitored speed (page
(3b) Time (B) has elapsed. The FSO module starts SLS monitoring (if not already
started).
Note: If the motor speed is not below the SLS monitoring limit after time B has elapsed,
the FSO module activates the SSE function. Depending on SSE function parameter
settings, the motor either coasts to a stop ("Immediate STO") or ramps down to zero
speed ("Emergency ramp"). For more information, refer to section
SSE function (page 36)
4.
The user or a PLC energizes the applicable digital inputs of the FSO module. This
deactivates the SLS request.
The FSO module acknowledges the SLS function automatically. This is set to be
automatic by an FSO parameter (SLSx.02), and no external acknowledgement input
is used. The FSO module stops SLS monitoring and de-energizes the digital output
that indicates the SLS status. The inverter unit returns to normal operation and starts
to follow its ordinary speed reference. The inverter unit accelerates the motor to the
desired speed along its acceleration ramp (inverter unit parameter).
5.
Normal operation continues.
and the FSO module user's manual.
Option description 19