OPERATION

3

3.1 Condition of use

The device must be a SIL variant to operate in SIL mode to perform the safety function.
INFORMATION!
Only properly trained and authorised personnel shall change device settings. Keep a report of
changes to the device settings. These reports must include the date, the menu item, the old
setting and the new setting.
The configuration is protected by a password. For more data on password protection and device
configuration refer to Switch to non-SIL operation on page 15.

3.2 Configuration of device for usage in safety application

Safety relevant parameters are write-locked and cannot be changed during safe operation.
Parameters which are not safety relevant can be changed in safe operation.

3.2.1 Change of operation mode

Non-SIL
operation
 Set safety mode
State
Non-SIL operation
Safe configuration
Safe operation
Table 3-1: Description of safety states
1 Icon shown at the local display or DTM.
14
Set safety mode
to SIL mode
to non-SIL mode
and confirm
Icon 1
-
Verify safe
parameters and
confirm
Safe
configuration
 Unlock device
Description
Device can be used in non-SIL
application and all
parameters can be changed.
Device can be configured for
safe operation or device can
be switched to non-SIL mode.
Device performs the safe
measurement according to its
configuration and all safety
relevant parameters are
locked.
www.krohne.com
OPTIFLUX X400
Safe operation
Safe current output
Measurement signal or
failure signal
Failure signal
Measurement signal or
failure signal
11/2021 - 4008790001 - AD OPTIFLUXx400 SIL R01 en