Gas High-High Alarm; System Fault Alarm - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

3.
Set the parameter RelayMode of the Gas High relay to On.
4.
On the H201Ci-1, verify that:
• The door-mounted 1 push-button indicator is lit.
• The Alarm 1 (Gas High) indicator (yellow, DS10; item 15 in Figure 3-7 on page 3-12)
is lit.
• The Alarm 1 NO contact is closed.
• The Alarm 1 NC contact is open.
• Other LED indicators and contacts have not changed from their previous state.
• If connected, the supervisory control and data acquisition (SCADA) system has detected
the alarm.
Note: Pushing the 1 push-button to acknowledge the gas alarm condition should not turn
off the indicator since the condition has not cleared.
8.2.4.2

Gas High-High Alarm

1.
Access the submenu Relays/Analog;GasHH Relay.
2.
Set the parameter RelayMode of the Gas High-High relay to On.
3.
On the H201Ci-1, verify that:
• The door-mounted 2 push-button indicator is lit.
• The Alarm 2 (Gas High-High) indicator (yellow, DS9; item 14 in Figure 3-7 on
page 3-12) is lit.
• The Alarm 2 NO contact is closed.
• The Alarm 2 NC contact is open.
• Other LED indicators and contacts have not changed from their previous state.
• If connected, the SCADA system has detected the alarm.
Note: Pushing the 2 push-button to acknowledge the gas alarm condition should not turn
off the indicator since the condition has not cleared.
8.2.4.3

System Fault Alarm

1.
Access submenu Relays/Analog;SysOK Relay.
Part 17997
Verification of Operation Prior to Installation
Rev. 6, March 2011
8-7