Directives And Declarations; Electromagnetic Compatibility, Industrial And Residential Areas - Siemens SIMATIC IPC277G Operating Instructions Manual

Hide thumbs Also See for SIMATIC IPC277G:
Table of Contents

Advertisement

Specific conditions of use (for ATEX)
• The modules shall be installed in a suitable enclosure providing a degree of protection of
at least IP54 according to EN 60079-7, taking into account the environmental conditions
under which the equipment will be used.
• Transient protection shall be provided that is set at a level not exceeding 140 % of the
peak rated voltage value at the supply terminals to the equipment.
Specific conditions of use (for IECEx)
• The equipment shall only be used in an area of not more than pollution degree 2, as
defined in IEC 60664-1.
• The modules shall be installed in a suitable enclosure providing a degree of protection of
at least IP54 according to IEC 60079-0, taking into account the environmental conditions
under which the equipment will be used.
• Transient protection shall be provided that is set at a level not exceeding 140 % of the
peak rated voltage value at the supply terminals to the equipment.
Switch:
SW1 On/Off switch - will not be used during operational maintenance
The device has to be used in pollution degree 2 environment only.
Use copper supply wires with a diameter of at least 0.75 mm
WEEE label (European Union)
Disposal instructions, observe the local regulations and the section "Recycling and disposal
(Page 69) ".
8.2

Directives and declarations

8.2.1

Electromagnetic compatibility, Industrial and Residential Areas

Electromagnetic compatibility
This product meets the requirements of EC Directive 2014/30/EU "Electromagnetic
Compatibility".
The device is designed for the following areas of application corresponding to the CE
marking:
Scope of application
Industrial area, residential,
commercial and light-industrial
SIMATIC IPC277G
Operating Instructions, 08/2021, A5E50059956-AA
Interference emission
EN 61000-6-3 +A1, CAN/CSA-CISPR
22:10
8.2 Directives and declarations
(= AWG18).
2
Requirements for
Immunity to interference
EN 61000-6-1, EN 61000-6-2, NAMUR NE 21
Technical specifications