Honeywell Home T6 Pro Smart Professional Install Manual page 5

Hide thumbs Also See for T6 Pro Smart:
Table of Contents

Advertisement

Available languages

Available languages

Setting Slider Tabs
Set R Slider Tab, see Figure 1.
• Use built-in jumper (R Slider Tab)
to differentiate between one or two
transformer systems.
• If there is only one R wire, and it is
connected to the R, Rc, or RH terminal
on the old thermostat, set the slider to
the up position (1 wire).
• If there is one wire connected to the R
terminal and one wire connected to the
Rc terminal, set the slider to the down
position (2 wires).
Set U Slider Tab, see Figure 2.
• Use built-in jumper (U Slider Tab) of
relay to wire ventilation. Please note
that ventilation is not supported on all
models.
• When the U Slider Tab is in the down
position (2 wires) the U contacts are a
dry set of contacts.
• If the ventilator is powered by the
cooling transformer, move the jumper
switch to the up position (1 wire). With
this switch set to 1 wire, the lower U
terminal is internally jumped to the Rc
terminal. In this application, hook up
one wire from the vent damper to the U
terminal and the other to the common
side of the cooling system transformer.
1
2
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Th6220wf2006Th6320wf2003

Table of Contents