L E D I N D I C ATO R S
CURRENT CONTROLLER BOARD 141-108
PWR
Power
BUS
Bus Status
HS1
Hall Sensor 1
HS2
Hall Sensor 2
HS3
Hall Sensor 3
TAC
Hall Sensor 4
Hall Sensor 5
ENBL
Enable
STALL
Stall Fault
PL
Power Loss
OV/UV
Overvoltage
UnderVoltage
IOC
Instantaneous
OverCurrent
PHAD
Phase Advance
1000AR
Model
Installation and Operation Manual
Turns ON GREEN as soon as power is applied to the drive.
Turns OFF when power is removed from the drive.
Turns ON RED as soon as power is applied to the drive
Changes to GREEN when voltage across charging resistor drops below 35VDC.
Changes back to RED if there is an OV/UV fault AND the drive is not enabled.
Changes back to GREEN when OV/UV fault is cleared.
Turns off when power is removed from the drive.
Turns on RED when SOUTH magnetic pole is over HS1 in encoder.
Turns off when NORTH magnetic pole is over HS1 in encoder.
Turns on RED when SOUTH magnetic pole is over HS2 in encoder.
Turns off when NORTH magnetic pole is over HS2 in encoder.
Turns on RED when SOUTH magnetic pole is over HS3 in encoder.
Turns off when NORTH magnetic pole is over HS3 in encoder.
Turns on GREEN when SOUTH magnetic pole is over HS4 in encoder.
Turns off RED when SOUTH magnetic pole is over HS5 in encoder.
Turns on BOTH when SOUTH magnetic pole is over both HS4 and HS5.
Turns off when NORTH magnetic poles are over both HS4 and HS5.
Turns ON YELLOW when:
1.
Drive is in RUN mode with no faults.
2.
Drive is in JOG mode with no faults.
3.
During RAMP STOP with no faults.
Turns off when:
1.
The UnderVoltage Timer times out.
2.
There is an Undervoltage (UV) fault.
3.
There is an OverVoltage (OV) fault.
4.
There is an IOC fault.
5.
There is a STALL fault.
6.
RUN, JOG, HOLD, and RAMP STOP modes are all off.
Turns ON RED if motor does not move 30° within specified time.
Time is inversely proportional to motor current.
Times out in 1.6 seconds at Current Limit (150% of full load).
Will not time out if current is less than 40% of full load.
Turns off when trips are reset.
Turns ON RED if the +24 VDC raw supply drops below 18VDC.
Turns ON RED if the +15VDC supply rises to within 3VDC of +24VDC.
Turns off when trips are reset if the condition no longer exists.
Turns ON RED in the following cases:
1.
Bus Voltage is greater than 120% of nominal at any time.
2.
Bus Voltage is less than 75% of nominal at any time.
3.
Bus Voltage is below 85% of nominal for 80 mS or more.
4.
The charging contactor is not energized.
Turns off when trips are reset if the condition no longer exists.
Turns ON RED if bus current to output transistors exceeds 300%.
Turns off when trips are reset.
Indicates electronic shifting of encoder signals to achieve Constant Horsepower.
GREEN indicates no phase advance.
ORANGE indicates 18° of phase advance timing.
RED indicates 30° of phase advance timing.
6/4/2001
© copyright 1997 by Powertec