CONNE CT AN OUTP UT CONTACTOR?
You MUST interlock the contactor with the Emergency Stop. You
WILL damage the drive if you do not interlock the contactor.
T3
T2
BLDC
G
MOTOR
THERMAL
contactor (such as AEG part number SH-04.40-ODC, which is
available from POWERTEC).
16
J
command and drops out ONLY on an emergency stop. The
contactor stays energized during normal stops.
RUN
JOG
# 156-012) for sequencing of contactors with AC coils.
CONNECTIONS WITH THE OUTPUT CONTACTOR.
CONNE CT DYNAMIC BRAKING?
TO MOTOR
THERMAL
Bus
Loader
Interlock
CONTACTOR
3 POLE n.c.
1 N.O. Aux
COIL < 230VAC
You may use an output contactor with the Model 1000AR.
Requirements for the Model 1000 series are:
1. The contactor must close its main power contacts
BEFORE it enables the drive;
2.
The contactor may only open its contacts AFTER
disabling the drive.
The contactor does not make or break current.
The figure at left shows the connections for a 48VDC output
In this configuration, the contactor pulls in on a run
POWERTEC makes an optional track mount PC board (Part
You MUST interlock the contactor with the
Emergency Stop when using Dynamic Braking. You will
damage the drive and/or the resistor banks if you do not
properly interlock the contactor.
The requirements are:
1.
The contactor must open the main power
contacts BEFORE the drive is enabled; AND
2. The contactor may only close its contacts
AFTER disabling the drive.
The AEG SH-04.13-ODC contactor is suitable to
the circuitry above. The figure on the left shows how to
use a POWERTEC 156-012 Contactor Control board to
control a larger contactor or a contactor with an AC coil.
In this configuration, the contactor energizes on a
run command and drops out ONLY on an emergency
stop. The contactor stays energized on a normal stop.