Advanced Heat Recovery with 3 Steps Electrical Heater
4.
Scenario
(With By-Pass Damper)
In this mode; exhaust and supply fans and after heater can be controlled.
Temperature is measured by room thermostate
If room temperature is measured below set value, temperature will be increased by using after heater
If room temperature is measured above set value,, temperature will be dccreased by shutting down the steps
of after heater till room thermostate readsroom temperature equal to set value
Note;
The electrical board comes with Scenario Number 4 as default.
To change the scenario please follow the steps defined in ''Changing the Scenario''
When Scenario 4 is selected , unit is ready to work as Advanced Heat Recovery with 3 Steps Electrical Heater (With By-Pass
Damper)
5. HEAT RECOVERY WITH 1 STEP PRE-HEATER 2 STEPS
Scenario
AFTER
Heat Recovery with 1 Step Pre Heater 2 Steps After Heater mode Works according to set temepareture and control exhaust
ans supply fans and after heater. Pre-heater works according to fresh air sensor.
Inside air temperature is measured by room thermostate
If room temperature is measured below set value, temperature will be increased by using after heater
If room temperature is measured above set value,, temperature will be decreased by shutting down the steps
of after heater till room thermostate reads room temperature equal to set value
The fresh air temperature read by NtC10K sensor will be compared with set value of pre-heater to open or
shut down pre-heater.
AFTER HEATER
TR