4136
135
Exhaust Fan 5. Step Value
4137
136
Exhaust Fan 6. Step Value
4138
137
Supply Fan 0. Step Value
4139
138
Supply Fan 1. Step Value
4140
139
Supply Fan 2. Step Value
4141
140
Supply Fan 3. Step Value
4142
141
Supply Fan 4. Step Value
4143
142
Supply Fan 5. Step Value
4144
143
Supply Fan 6. Step Value
4145
144
Fire Scenario Selection
4146
145
Cooling and Heating Hysteresis Value
4147
146
Pressure Error Quantity
4148
147
Pressure Error Period
4149
148
Maximum working time for boost
4150
149
Heater Limiting according to Fan
4151
150
Pre Heater Delay time at Start
4152
151
Pre Heater Delay time at Stop
4153
152
Pre Heater Hysteresis Value
4154
153
Pre Heater Steps as Temperature
4155
154
Pre Heater Step Quantity
4156
155
After Heater Opening Delay Time
4157
156
After Heater Stopping Delay Time
After Heater Hysteresis Value
4158
157
4159
158
After Heater Steps as Temperature
4160
159
After Heater Step Quantity
4161
160
Pre Heater Set Temperature
4162
161
ByPass Histeresis Value
4163
162
Rotary Exchanger Histerezsis Value
4164
163
Valve P Value
4165
164
Valve I Value
4166
165
Compressor Starting Time
4167
166
Compressor Stopping Time
4168
167
Compressor Histeresis Value
4169
168
Fan Step in case of defrost
Min. Temperature Value for defrost
4170
169
Pressure Error Parameters
Boost ve Heater Limiting Parameters
Pre Heater Setting Parameters
Last Heater Setting Parameters
Accessories Setting Parameters
PID Setting Parameters
Compressor Setting Parameters
Compresor Defrost Setting Parameters
It is recommended not to work motor , at
a value of exit voltage under 120 V.
0-100
0: Shut down both fans
1: Exh. Fan Full Supp. Fan.Off
0-3
2: Exh. Fan Off Supp. Fan.Full
3: Both fans are working
0-999
For instance, if the value is 5 and
0-10 each
there happens 5 pressure error
,unit shuts down. F the values is 0
then unit will shut down with the
first pressure error.
1-30min.
0-999min
Boost will close at the end of this period
0-1
1-999 Sec.
1-999 Sec.
1...100
100 value means 10.0ºC
0-3
1-999 Sn
1-999 Sn
1...100
100 value means 10.0ºC
-400...999
1...999
1...999
1...999
1...999
Starting and Stopping Time of
1...100
Compressor can be set.
0...6
-400...999