4111
110
Service Setting Password
4112
111
Modbus ID
4113
112
Modbus Baudrate
4114
113
Show Temperature Value
4115
114
Show Analog Inlet
4116
115
Filter Dirtiness Counter
4117
116
Unit Mode Info
4118
117
Activate Boost
4119
118
Temperature Check Point
119
Exhaust/Fresh Air Damper Opening Period
4120
4121
120
Auto Mod Fan Min. Speed
4122
121
Full Auto Mod Fan Working Stage
4123
122
Full Auto Mod Exhaust Fan Value
4124
123
Full Auto Mod Supply Fan Value
4125
124
Full Performance of the Fans at the start
4126
125
Passage time between fan steps
4127
126 Fan Hysteresis Value
4128
127
The difference value between the fans
4129
128
Fan delay time at the start
4130
129
Fan working time after stop command
4131
130
Exhaust Fan 0. Step Value
4132
131
Exhaust Fan 1. Step Value
4133
132
Exhaust Fan 2. Step Value
4134
133
Exhaust Fan 3. Step Value
4135
134
Exhaust Fan 4. Step Value
Building Management Modbus-RTU Parameters
Screen Value Registers
Filter Time Counter Parameters
Boost Mode Setting Registers
Parameters for Temperature Check Point
Auto Mode Fan Setting Parameters
0...9999
Main card password is "58"
1...254
0...7
0:Do Not Show
1:OutsideTemperature
0...3
2:Supplied Air Temperature
3:Show both temperatures
0:Do not show
1:CO2
0...3
2:Air Quality
3:Humidity
Counter increases due to working hour
0-9999hour
of supply fan
0:Unit Off
1:Damper is opening
2:Fan Starts Working
3:Main Function
0-100
4:Valve Closing
5:Fan Stops
6:Frost
7:Defrost
99:Error Mode (Waiting for Reset)
0:Deaktive
0-1
1:Aktive
0:Controller
1:Return Air Temperature
0-3
2:Supply Air Teperature
3:Outside Air Temperature
Opens damper and start fans and
0-999sec.
other components after waiting for
the period defined here
The minimum speed for fans at
0-6
auto mod
0: Normal
0-1
1: Working Continously
0-100
Working value for Exhaust Fan
0-100
Working value for Supply Fan
Full Performance for the fans or not at
0-1
the start
0—999sec.
Passage time between fan steps
If fans work thermostatically, the
0-999
hysteresis value between step
changing..
0-999
0-999sec.
Waiting time for the fan to start
Waiting time for fans to stop after stop
command (Cools electrical heater and
0-999sec.
other components after they stop
during the delay time.)
0-100
It is recommended not to work motor ,
at a value of exit voltage under 120 V.