N.

ERROR CODES TROUBLE SHOOTING

CODE
EXPLANATION
E
0001
Exhaust Fan Error
E
0002
Supply Fan Error
E
0004
Electrical Heater Error
E
0008
Exhaust Air Flow Error
E
0016
Supply Air Flow Error
E
0099
Connection Error between
Controller and Card
E
0256
Fire Alarm
Check the fan,connection cables and filter.If 11lla re fine,
reset the alarm by pressing
simultaneously If there is a broken component replace it
with a new one.
Check the fan,connection cables and filter.If 11lla re fine,
reset the alarm by pressing
simultaneously If there is a broken component replace it
with a new one.
Check the electrical heater and connection cables ..If 11lla
re fine, reset the alarm by pressing
simultaneously If there is a broken component replace it
with a new one.
Check the exhaust fan,connection cables ,filter and
ducting..If 11lla re fine, reset the alarm by pressing
and
UP
buttons simultaneously If there is a broken
component replace it with a new one.If there is an
obstacle at the duct systemi, clean it a for a better air
flow.
Check the exhaust fan,connection cables ,filter and
ducting..If 11lla re fine, reset the alarm by pressing
and
UP
buttons simultaneously If there is a broken
component replace it with a new one.If there is an
obstacle at the duct systemi, clean it a for a better air
flow.
Check connection cables between controller and the
board
Check if there is fire or not.. If the alarm is because of a heat
transmitter close to room thermostate , or another factor that
increases the temperature at the room artificially, make sure
that the room thermostate reads the temperature at the normal
conditions. Also check the electrical heater at the duct system.
If everything is controlled then reset the alarm by pressing
and
UP
buttons simultaneously.
FAN
and
UP
buttons
FAN
and
UP
buttons
FAN
and
UP
buttons
FAN
FAN
FAN

Advertisement