User Section - Ei Electronics Ei140e Series Instruction Manual

230v smoke & heat alarms

Advertisement

3. Maintaining your Alarm
3.1 Testing your Alarm
Frequent testing of all your Alarms is a requirement to
ensure they are functioning correctly. Guidelines and
best practices for testing are as follows:
1. After the system is installed.
2. Once monthly thereafter.
3. After prolonged absence from the dwelling (e.g. after
holiday period).
4. After repair or servicing of any of the systems
elements or household electrical works.
Inspecting and Testing procedure
Check power
Check that there is a constant green light
Press the test/hush button for 10 seconds.
(i) Check that the green LED power indicator is on
continuously. (If it is off, check circuit breakers, fuses
and wiring etc.)
(ii) Check that the red LED on the cover flashes once
every 40 seconds to indicate normal operation – If
the memory has been set indicating that the Alarm
has been activated in the last 24 hours, the red LED
will flash twice every 40 seconds. After 24 hours,
the memory will be cleared or if the Test button is
pressed.
(iii) Check also that there are no faults i.e. NO chirps (if
this is the case please see indicator summary table).

User Section

on the cover
Test
The Alarm will sound loudly
17