4. Installation method (continued)
Wire connection diagram
* TM1, TM2, TM3, TM4, TB5 shown in dotted lines are field work.
* Be sure to connect the ground wire.
* A power supply isolator must be installed.
* Always use an isolator for the main switch power connection.
* Select proper circuit breaker according to the electrical current information in the chart below.
* Do not disconnect connectors.
Model
Maximum current when
operating [A]
Inrush current after
10 ms
power supply ON
100 ms
[A]
Operation signals
Lossnay remote controller
(Max. 2) and 2nd Lossnay
(Max. 15 units)
M-NET transmission
cable
12 V or 24VDC
or Mr. Slim
Volt-free contact
LGH-F300RVX2-E LGH-F380RVX2-E LGH-F470RVX2-E LGH-F600RVX2-E LGH-F940RVX2-E LGH-F1200RVX2-E
3.40
3.10
9
10
1
2
A
B
S
Shielded wire
1
2
TM2
Y
Z
TM1: Terminal block (Power supply)
TM2: Terminal block (External control input)
TM3: Terminal block (Monitor output)
TM4: Terminal block (Transmission cable)
TB5: Terminal block (M-NET transmission cable)
4.05
6.1
3.6
TM3
Printed Circuit Board
TM4
TB5
TM1
L
N
Isolator
(Field supply)
Eng-7
4.15
8.10
12.2
7.2
Power supply
208-230 V / 60Hz
8.30