5. Function settings (continued)
No.67
Threshold minutes for PZ-70CSW-E LED
LED turns from orange (MID) to red (HIGH) when the CO
kept over the limit concentration for decided minutes.
The threshold minutes can be changed.
Refer to the Installation manual of PZ-70CSW-E for more detail.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
67
N/A
-
-
-
-
-
-
Threshold concentration for PZ-70CSW-E
No.68
LED
The threshold concentration for wall mounted CO
green (LOW) to orange (MID) can be changed.
Refer to the Installation manual of PZ-70CSW-E for more detail.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
-
-
68
-
-
-
-
-
-
-
-
-
-
No.69
Emergency stop setting
This function can select the priority of Remote OFF signal to CN32.
When the emergency stop is selected and Lossnay receives remote
off signal, Lossnay does not operate Night purge, after cooling or
some other operations until remote off signal stops.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
69
-
-
- When installing the centralized management devices (including the
system controller) in Mitsubishi Electric Air-Conditioner Network
System (MELANS), perform emergency stop by the centralized
management devices. In this case, do not use the function
level is
2
Setting
Threshold minutes for
check
PZ-70CSW-E LED
0
10 min
1
15 min
2
20 min
(Factory setting)
3
25 min
4
30 min
sensor LED from
2
Setting
Threshold concentration
check
for PZ-70CSW-E LED
0
1000 ppm
1
1100 ppm
2
1200 ppm
3
1300 ppm
4
1400 ppm
5
1500 ppm
(Factory setting)
6
1600 ppm
7
1700 ppm
8
1800 ppm
9
1900 ppm
10
2000 ppm
Lossnay
Setting
Mode
operation
check
When stopped
by Remote
OFF input,
Emergency
Night purge,
0
(Factory setting)
stop
after cooling
and some other
operation does
NOT work.
When stopped
by Remote
OFF input,
Normal
Night purge,
1
stop
after cooling
and some other
operation does
work.
No. 69
.
Eng-24