5. Function settings (continued)
No.28
Pulse input setting
Set external input signal type from external device for TM2.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
SW2-2
28
(Factory setting)
ON
When pulse signal is selected,
Keep factory settings for
No. 9
Either interlocking with City multi or Mr. Slim is not possible.
Night-purge setting 1)
No.30
Air volume
Set fan speed during Night-purge. To use Night-purge function, it is
necessary to set
,
No. 30
No. 31
This function is N/A from Lossnay unit DIP-SW.
It can also be set on the PZ-62DR-E's Ventilation settings screen.
When using PZ-62DR-E and AE-200A together, set all conditions
from AE-200A.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
N/A
30
-
-
-
-
-
-
Night-purge setting 2)
No.31
Outdoor and indoor temperature gap
Set one of conditions for Night-purge start, temperature gap between
indoor and outdoor.
When the actual gap between indoor and outdoor becomes bigger
than the setting, Night-purge starts.
This function is N/A from Lossnay unit DIP-SW.
When using PZ-62DR-E and AE-200A together, set all conditions
from AE-200A.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
N/A
31
-
-
-
-
-
-
-
-
Setting
Pulse input setting
check
0
DIP-SW priority
(Factory setting)
1
NOT pulse input
2
Pulse input
and
are not available.
No. 9
No. 19
and
.
No. 19
,
correctly.
No. 32
Setting
Air volume
check
N/A (Night-purge
0
(Factory setting)
function is not available)
1
Fan speed 1
2
Fan speed 2
3
Fan speed 3
4
Fan speed 4
Setting
Outdoor and indoor
check
temperature gap
0
0 K (0 °F/0 °C ) or more
1
1 K (1.8 °F/1˚C) or more
2
2 K (3.6 °F/2˚C) or more
3
3 K (5.4 °F/3˚C) or more
4
4 K (7.2 °F/4˚C) or more
5
5 K (9 °F/5˚C) or more
(Factory setting)
6
6 K (10.8 °F/6˚C) or more
7
7 K (12.6 °F/7˚C) or more
Night-purge setting 3)
No.32
The lowest outdoor temperature
Set one of conditions for Night-purge start, maximum outdoor
temperature within 72 hours.
When this setting temperature is low, it is likely to start Night-purge.
This function is N/A from Lossnay unit DIP-SW.
When using PZ-62DR-E and AE-200A together, set all conditions
from AE-200A.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Night purge setting 4)
No.33
Outdoor temperature detection period
Night-purge is decided to start or not by the OA temperature within X
hour.
X hour can be selected from 24, 48 or 72 hrs.
It is possible to operate Night-purge on Sunday midnight or Monday
early morning by select longer setting even Lossnay stops.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
N/A
-
-
No.34
Input priority setting
Set to follow input to the main unit from air conditioner, fan speed
controller, etc.
When multiple Lossnay units fan speed is externally controlled via
CN17 or CN26, select individual control or bunch control.
When bunch control is selected, connect PZ-62DR-E and input
external signal to the main unit.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
Eng-19
PZ-62DR-E
Setting
The lowest outdoor
check
temperature
Function No. Setting Data
0
59 ˚F (15 ˚C) or more
1
61 ˚F (16 ˚C) or more
2
63 ˚F (17 ˚C) or more
(Factory setting)
3
64 ˚F (18 ˚C) or more
4
66 ˚F (19 ˚C) or more
5
68 ˚F (20 ˚C) or more
6
70 ˚F (21 ˚C) or more
7
72 ˚F (22 ˚C) or more
32
8
73 ˚F (23 ˚C) or more
9
75 ˚F (24 ˚C) or more
10
77 ˚F (25 ˚C) or more
11
79 ˚F (26 ˚C) or more
12
81 ˚F (27 ˚C) or more
13
82 ˚F (28 ˚C) or more
14
84 ˚F (29 ˚C) or more
15
86 ˚F (30 ˚C) or more
PZ-62DR-E
Setting
OA temperature
check
detection period
Function No. Setting Data
0
24 hrs
1
48 hrs
33
2
72 hrs
(Factory setting)
PZ-62DR-E
Setting
Input priority setting
check
Function No. Setting Data
0
Bunch control priority
(Factory setting)
34
1
Individual control priority