Mitsubishi Electric LGH-F300RVX2-E Installation Instructions Manual page 26

Lossnay energy recovery ventilator
Hide thumbs Also See for LGH-F300RVX2-E:

Advertisement

Available languages

Available languages

5. Function settings (continued)
No.83, 84
Filter maintenance interval setting
Filter cleaning sign is displayed on the remote controller according to
the set interval in this function.
The interval can be set from 100 hrs to 9900 hrs depending on the
site situation.
This function can also be set on the Maintenance interval settings
screen of the PZ-62DR-E.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
83
-
-
-
-
-
-
-
-
-
-
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
84
-
-
-
-
-
-
-
-
-
-
Lossnay core maintenance interval
No.85, 86
setting
Lossnay core maintenance sign is displayed on the remote controller
according to the set interval in this function.
The interval can be set from 100 hrs to 9900 hrs depending on the
site situation.
This function can also be set on the Maintenance interval settings
screen of the PZ-62DR-E.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
85
-
-
-
-
-
-
-
-
-
-
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
86
-
-
-
-
-
-
-
-
-
-
Setting
Filter maintenance interval
check
setting - Thousands digit
0
0
1
1
2
2
3
3
(Factory setting)
4
4
5
5
6
6
7
7
8
8
9
9
Setting
Filter maintenance interval
check
setting - Hundreds digit
0
0
(Factory setting)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
Setting
Lossnay core maintenance
check
interval setting - Thousands digit
0
0
1
1
2
2
3
3
4
4
5
5
6
6
(Factory setting)
7
7
8
8
9
9
Setting
Lossnay core maintenance
check
interval setting - Hundreds digit
0
0
(Factory setting)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
No.89, 90
CO
It is possible to set the CO
4.
When it is necessary to set 50 ppm, set Function
This function can also be set on the CO
PZ-62DR-E.
(For example, the target is 950 ppm, Function
No. 90
is 1.)
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
No.91, 92
CO
It is possible to set the CO
1.
When it is necessary to set 50 ppm, set Function
This function can also be set on the CO
PZ-62DR-E.
(For example, the target is 950 ppm, Function
is 1.)
No. 92
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
Eng-26
sensor setting - maximum side
2
concentration which fan speed turn into
2
No. 90
control setting screen of the
2
No. 89
CO
sensor setting
PZ-62DR-E
2
Setting
- maximum side -
check
Function No. Setting Data
Hundreds digit
0
600 ppm
1
700 ppm
2
800 ppm
3
900 ppm
4
1000 ppm
(Factory setting)
5
1100 ppm
6
1200 ppm
89
7
1300 ppm
8
1400 ppm
9
1500 ppm
10
1600 ppm
11
1700 ppm
12
1800 ppm
13
1900 ppm
14
2000 ppm
CO
sensor setting -
PZ-62DR-E
2
Setting
maximum side - Tens
check
Function No. Setting Data
digits
0
0 ppm
(Factory setting)
90
1
50 ppm
sensor setting - minimum side
2
concentration which fan speed turn into
2
No. 92
control setting screen of the
2
No. 91
CO
sensor setting
PZ-62DR-E
2
Setting
- minimum side -
check
Function No. Setting Data
Hundreds digits
0
300 ppm
1
400 ppm
(Factory setting)
2
500 ppm
3
600 ppm
4
700 ppm
5
800 ppm
6
900 ppm
91
7
1000 ppm
8
1100 ppm
9
1200 ppm
10
1300 ppm
11
1400 ppm
12
1500 ppm
13
1600 ppm
14
1700 ppm
CO
sensor setting -
PZ-62DR-E
2
Setting
minimum side - Tens
check
Function No. Setting Data
digits
0
0 ppm
92
1
50 ppm
(Factory setting)
as 1.
is 3 and
as 1.
is 6 and